lbx INCR-070-001 Скачать руководство пользователя страница 7

 

7

 

 

2.

 

Check ambient Temperature 

Press the set button for more than 3 seconds, it 

will show “LC”, 

change i

t to “18” 

using up and down keys. Click 

set button and screen will show the ambient temperature. Press set button 3 seconds to exit this screen, the 
specification will keep automatically. If during 30 seconds, no button is pressed, it will exit settings automatically 
and will not keep the specification. 
 
 
 
 
 
 
 
 

3.

 

Compressor operating mode and frost related parameters 

Press the set button for more than 3 seconds, it 

will show “LC”, 

change 

it to “123” 

using up and down keyboard, 

click set button, can check the internal parameter value. Press the SET key to change parameters and up and 
down arrows to modify each parameter value and then click SET button for more than 3 seconds to leave this 
screen, the specification will keep automatically. If during 30 seconds, no button is pressed, it will exit settings 
automatically and will not keep the specification. 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

Paramet
er 

Name 

Function 

(Range)factory 
value 

Lc- 

Password 

when“Lc=18”, we can check the ambient 

temperature. 

 

Hd- 

Ambient 
temp. 

 

 

Parameter  Parameter Function 

(range)Factory value 

Lc

-

 

“Lc=123”can see and modify each parameter.

 

 

S-H 

When “ambient temp.

-

SH” > Temp. Setting value, 

the compressor normally open operation. On the 
contrary, the compressor break-off work. 

Note: when” S

-

H=50.0”, the compressor doesn’t 

work. 

-20.0

50.0

 

40

.

Ft- 

Fan delay, stop the fan when frost;After frost 
melting, fan delay Ft- second start. 

(0

99s)50S 

dt1 

SP≤15

 Frost interval 1 

(0

250Hours) 

12Hours 

Hs1 

Frost melting output 1

 

(0

250S) 60S 

dt2 

15

<SP

30

 Frost interval 2 

(0

250Hours) 

12Hours 

Hs2 

Frost melting output 2

 

(0

250S) 55S 

HA 

Compressor switched on and off automatically. 
1 is to automatically judge the switch compressor 
according to the ambient temperature. 
0 is to control the compressor on and off according 
uP and dn. 

0

1

cH 

Frosting and evaporator switching options, 0 for 
frosting, 1 for evaporation switching

 

0

1

0

 

Содержание INCR-070-001

Страница 1: ...LBX INC R Refrigerated Incubator Please read the User Manual carefully before use and follow all operating and safety instructions user manual english ...

Страница 2: ...ith the following information Serial number Description of the problem Your contact information Warranty This instrument is guaranteed to be free from defects in materials and workmanship under normal use and service for a period of 24 months from the date of invoice The warranty is extended only to the original purchaser It shall not apply to any product or parts which have been damaged on accoun...

Страница 3: ...licon 7 50mm diameter test hole Product specifications Model INCR 070 001 INCR 150 001 Voltage 220 240V 50Hz 60Hz Temp Range 0 65 Temp Motion 0 5 Temp Uniformity 1 Cryogen R134a Power 800W 1000W Inner Chamber size cm 35 x 41 5 x 50 40 x 49 x 75 Exterior Size cm 56 x 57 x 103 62 x 64 x 129 Inner Chamber Temp Distribution map 9 7 8 4 1 3 2 6 5 Temperature Graph 30 20 10 0 30 60 10 20 30 40 50 60 30 ...

Страница 4: ...you add one working equipment into the chamber if the power is bigger than 2A plug the power outside do not use this equipment power 6 When the chamber temp 50 please do not set the low temp settings to make sure the compressor can be used for a long time 7 Anyone who operates the equipment must first read this manual Operation cautions 1 There is a test hole at the top of the incubator If you add...

Страница 5: ... 30 seconds press the down keyboard for 4 seconds the system will start working again when the buzzer sounds please click any keyboard to stop the sound 3 Illumination click the illumination button and then it will turn on click again and it will close Without timer setting With timer setting ⅳ Inner Chamber Specification setting Press the set button for more than 3 seconds the screen will show LC...

Страница 6: ...uP and compressor delay time out then compressor begin to work 50 0 50 0 0 2 Dn Cooling refrigeration backlash compressor in manual model when PV SP dn the compressor shut down 51 0 uP 0 1 0 T Control cycle 1 60sec 5 P Proportional band 1 0 measure value 35 I Integration time 1 1000sec 200 d Differential time 1 1000sec 200 Pb 0 adjust Sensor zero display error adjusts Pb actual temp display number...

Страница 7: ...n is pressed it will exit settings automatically and will not keep the specification Paramet er Name Function Range factory value Lc Password when Lc 18 we can check the ambient temperature Hd Ambient temp Parameter Parameter Function range Factory value Lc Lc 123 can see and modify each parameter S H When ambient temp SH Temp Setting value the compressor normally open operation On the contrary th...

Страница 8: ...en Check the ice or oil block Specification mixed Setting correct and restart Temp up continue Evaporator frost Dry the chamber Abnormal Knocking Circle Fans loose Check and adjust Condenser Fan compressor loose Check and adjust or contact with us Bad evenness degree Sample hot Reduce sample quantity Evaporator frost wind block Dry the chamber Restart Controller instability Power do not match Chan...

Страница 9: ... vertederos De conformidad con la Directiva 2002 96 CE los usuarios de la Unión Europea de aparatos eléctricos y electrónicos tienen la oportunidad de retornar el instrumento para su eliminación al distribuidor o fabricante del equipo después de la compra de uno nuevo La eliminación ilegal de aparatos eléctricos y electrónicos es castigada con multa administrativa Les appareils électriques et élec...

Страница 10: ...www labbox com ...

Отзывы: