   Enclosed documentation (flow rate curves, op-

erating characteristic diagrams, dimension sheet, 
spare parts list, spare parts drawing and Declara-
tion of Incorporation)

Type label

Maximum burner capacity, gas type – see type label.

http://www.lbe-online.de

type

 ECOMAX

nom capacity

   

kW

fuel

Installation

 CAUTION

 We recommend that lifting gear be used for instal-

lation due to the weight involved.

 

With the ECOMAX

®

..C, the air guide tube is sup-

plied separately to prevent transport damage 
or is fitted with extra transport protection. See 
attached documentation.

Installation on the furnace

 

The burner has three connectors for air and one 

for flue gas. During installation, the burner must 
be aligned appropriately (flue gas upwards or 
to the side).

ECOMAX

®

 for direct heating systems

 

For a direct heating system, the flue gas guide 
tube FGT kit..D and the eductor EJEK are re-
quired, see page 14 (Accessories).

EJEK

FGT kit..D

EJEK

  

 Remove the transport safety device.

 

If the diameter of the furnace insulation is greater 
than the external diameter of the flue gas guide 
tube, wrap the flue gas guide tube with a fibre 
mat before installing the burner.

3

4

2

5

 

Tighten the nuts in two cycles in a crosswise 

fashion, torque: 46 Nm.

 

When installing, always ensure that when the 

burner is mounted, it is sealed tightly on the 
furnace.

Installing the eductor

 

The eductor is mounted to the side of the burner.

 

Align the eductor’s pressure test point to the 

control side.

1

3

2

 

Use the correct torque so that the housing is 
not damaged.

Type

Torque

ECOMAX

®

 1

26 Nm

ECOMAX

®

 2

26 Nm

ECOMAX

®

 3

30 Nm

ECOMAX

®

 4

35 Nm

ECOMAX

®

 5

35 Nm

 

After installing the eductor, connect the 

 ECOMAX

®

 to the air and gas circuits.

ECOMAX

®

 for indirect heating systems

 

For an indirect heating system, the ra-
diant tube  SER, the segmented flame 
tubes  SICAFLEX

®

 and

 

the flue gas connec-

tor FLUP are required, see page 14 (Acces-
sories).

Содержание ECOMAX Series

Страница 1: ...s technicians Electrical interventions may only be carried out by qualified electricians Wear protective clothing for all installation and maintenance work to prevent injuries Conversion spare parts A...

Страница 2: ...2 P03 Gas flange with purging air connection K3 Additional cooling air connection A3 Kanthal electrode DA13 DA23 Differential air pressure measuring kit Differential air pressure measuring kit with pr...

Страница 3: ...it D and the eductor EJEK are re quired see page 14 Accessories EJEK FGT kit D EJEK 1 Remove the transport safety device If the diameter of the furnace insulation is greater than the external diameter...

Страница 4: ...flange and SER M Install the internal segmented flame tubes SICAFLEX see www docuthek com Elster Kromschr der Kromschr der LBE Prod ucts 07 Pilot burners and burners Self recuperative burner ECOMAX S...

Страница 5: ...this pur pose see page 10 Replacing the gas lance If necessary another air connection may be used The burner has three air connections two of which are sealed with blind flanges Ensure undisturbed fl...

Страница 6: ...particular avoid external electrical interference when using ionization control For UV control route the ignition cable separately from the UV cable 1 3 2 4 Connect the PE wire for grounding to the g...

Страница 7: ...s are installed in the gas and combustion air connections on the burner Adjustment is made on the basis of the flow rate dependent pressure differential The required pressure differentials for gas and...

Страница 8: ...ative flue gas pressure on the motive air restrictor Pressure switch If the burner is equipped with a pressure switch on the air connection to monitor the flow the switching point should be set to app...

Страница 9: ...substoichiometric operation of the burner If necessary adjust the settings of the combustion air and motive air 11 Check the differential pressures pgas and pair and the negative flue gas pressure pF...

Страница 10: ...ast 5 A and must not vary Read off the ionization signal on the burner con trol unit 3 Disconnect the system from the electrical power supply 4 Shut off the gas and air supply do not change the restri...

Страница 11: ...procedure when reassem bling We recommend that the burner be removed to allow a more accurate inspection 26 27 If the insulation is worn or damaged it must be replaced Checking replacing the air guide...

Страница 12: ...nsu lation together e g using adhesive tape Tighten the nuts in two cycles in a crosswise fashion 40 41 Tighten the nuts in two cycles in a crosswise fashion Torque for ECOMAX 1 3 18 Nm ECOMAX 4 5 35...

Страница 13: ...s detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance with the relevant operating instructions Faults Cause Remedy Burner does not functio...

Страница 14: ...gs Check the gas and air pressures Automatic burner control unit signals a fault Check the ionization cable Check the ionization current The ionization cur rent must be at least 5 A stable signal Mixi...

Страница 15: ...t Eco 2 5 E 22801111 P2 set Eco 4 0 E 22801108 P3 set Eco 2 5 B 22801107 P3 set Eco 4 0 B 22801106 Technical data Heating direct with eductor or indirect in radiant tube Control type On Off Control ra...

Страница 16: ...C Annex II No 1B The product Self recuperative burner for gas ECOMAX is a partly completed machine pursuant to Article 2g and is designed exclusively for instal lation in or assembly with another mach...

Страница 17: ...GB 17 D GB...

Страница 18: ...8 0 F 49 202 60908 20 GB 18 GB F NL I E Contact If you have any technical questions please contact your local branch office agent The addresses are available on the Internet or from Elster GmbH We res...

Отзывы: