Emergency Eye Wash Valve

(1)

Installation &

Maintenance Manual

M EFV D

PAT. NO. 5,011,074.

PAT. NO. 5,379,936.

Setting the Mixing Valve

Caution: When maintaining and adjusting the mix-

ing valve, all fixtures should be isolated from use.     

Lawler  Manufacturing  Co.,  Inc.  recommends  that 

you work safely at all times and in a manner con-

sistent  with  the  OSHA  Lock/Tagout  standard,  29 

CFR 1910.147 and other applicable standards.

This  mixing  valve  has  been  set  at  the  factory  

to deliver 85°F outlet flow. Should the valve require 

adjustment, or an application require a different set 

temperature, proceed as follows:
1.  Contact the proper medical and safety authorities 

to  determine  the  correct  water  temperature  for 

the specific application (ie. chemicals).

2.  Remove  the  rounded  cover  nut  on  front  of  the 

valve body.

3.  Create a draw on the mixing valve by opening a 

downstream eye wash fixture.

4.  Insert a 

5

/

32

 allen key into the stem opening of 

the valve and seat in the adjustment screw (not 

shown). Set the outlet temperature by turning the 

adjustment screw clockwise to reduce tempera-

ture, counterclockwise to increase temperature. 

Use the dial thermometer to measure the outlet 

temperature.

5.  Replace rounded cover nut.

 

Operating Principle

This  Series  911  Emergency  Eye Wash/Face Wash 

mixing valve is made of a thermostat element with 

a stainless steel sliding piston and liner housed in a 

bronze casting. The thermostatic cartridge responds 

to  temperature  changes  in  the  hot  and  cold  water 

supplies. In the event the thermostatic element fails 

or the hot water supply fails, the valve will provide 

full cold water bypass flow.

Note:  Valve must be installed with check valves.  

If shut off valves are installed in the shower line 

for  maintenance  purposes,  provisions  shall  be 

made to prevent unauthorized shut off.

Caution: When maintaining and adjusting the mix-

ing valve, the delivered flushing fluid temperature 

shall  be  60°F  (15°C)  to  95°F  (35°C).  In  circum-

stances  where  chemical  reaction  is  accelerated 

by  flushing  fluid  temperature,  a  medical  advisor 

should be consulted for the optimum temperature 

for each application.

www.lawlervalve.com

CAPACITIES – MODEL 911E/F

 

 

 

Pressure Drop PSI  

5

 

10

  20  30  45

 

Tempered Flow   

2

 

3

 

5

 

7

 

10

  Cold Water Bypass 

1

  

2

 

4

 

5

 

7

30

40

50

60

70 80

90

110

120

130

5330 East 25

th

 Street

Indianapolis, Indiana 46218

Phone (317) 261-1212

Fax (317) 261-1208