(3)

 

Figure 1

Typical installation. Valve must be 

installed with check valves.

Figure 2

Typical installation. Valve must be 

installed with check valves.

Installation

After installing the mixing valve, be sure to flush the 

system of debris. Lawler recommends isolation and 

check valves for proper maintenance.
Typical Installation 

Figure 1

When installed without a recirculation system:
Install the valve as shown in 

Figure 1

 with the mixing 

valve positioned below the hot water tank or heater.  

If this is not possible, pipe in heat trap as shown.
Typical Installation 

Figure 2

When installed with a recirculating pump on the hot 

water supply line only:
Note: If the valve is installed 20 feet or more from 

the water heater, it is important to recirculate the hot 

water supply to the mixing valve.
Install  the  mixing  valve  as  shown  in 

Figure  2

. The 

non-circulated loop should be limited to 10 feet and 

must be flushed periodically.

Caution:  The  cold  water  line  must  be  installed 

so  that  it  is  not  affected  by  excessively  hot  am-

bient  temperatures.  Provisions  shall  be  made 

to  thermally  isolate  the  valve.  Cold  water  pipe 

installed in the ceilings of boiler rooms or rooms 

that  increase  ambient  temperature  require  a  re-

circulating pump.  

GuARANTEE

We  guarantee  the  Lawler  Mixing  Valve  to  be  free  

from  defects  in  workmanship  and  material,  and,  

for  a  period  of  one  year  from  date  of  purchase, 

will  replace  any  parts  found  by  Lawler  Manufac-

turing Co., Inc. to be defective. We will not be held  

responsible,  however,  for  any  labor  incidental  to, 

or  for  any  damages  caused  by,  defective  material. 

Each mixing valve is thoroughly inspected and tested 

under actual conditions at our factory.

Note: The mixing valve must be installed with 

inlet check valves and the Eyewash/Facewash 

fixture  should  be  installed  4  to  10  feet  from 

the mixing valve. 

Note: The valve body must be maintained at an 

ambient room temperature of above 50°F to pre-

vent  premature  closure  of  the  safety  back-seat 

mechanism.

Water

Heater

Storage

Tank

Eye/Face 

Wash

Series 911E/F

CW

Heat Trap

27

 Drop

HW

Water

Heater

Storage

Tank

Series 911E/F

CW

Heat Trap

27

 Drop

Recirculating Pump

1 valve per 

eye wash fixture

Maximum Inlet Pressure: 125 PSI.
Recommended Supply Pressure: 65 PSI.
Recommended Inlet Temperature: 120

°

F.

*

*

When supplying 140°F or greater, additional outlet 

controls should be used.

Warning: This product contains chemicals known to the 

State of California to cause cancer and birth defects or 

other reproductive harm.

(Installer:  California  law  requires  that  this  warning  be 

given to the consumer.)
For more information: www.oehha.org/prop65