Setting The Mixing Valve To The System

Typical Installation

Install  the  mixing  valve  below  the  hot  water  tank  or 

heater.  If this is not possible, pipe in a heat trap as  

shown in Figure 1 with an approximate 27

 drop.

Connect  a  tempered  water  return  line  as  shown  in  

Figure  1.  This  allows  flow  through  both  ports  of  the 

mixing valve during periods of no draw.
If  a  dual  temperature  system  is  used,  a  separate  re-

circulating  loop  and  pump  are  required  to  return  high 

temperature hot water to the water heater.  See Figure 2.
Install an aquastat at the tempered water return pump.
Install the water heater per manufacturer’s instructions.  

 

 1.  After installation be sure to flush the system thor-

oughly.

 2.  Make sure the hot water supply is heated to normal 

design temperature.

 3.  Close  and  tag  all  fixtures  to  ensure  they  are  not 

used during this procedure.

 4.  Turn off the recirculating pump.
 5.  Create  a  draw  on  the  system  greater  than  the 

minimum flow rating of the mixing valve.  All open 

fixtures  must  be  tagged  to  ensure  they  are  not 

tampered with or used during this procedure.

 6.  Allow water to flow through the mixing valve until 

the  water  temperature  is  stable.    If  necessary, 

readjust the mixing valve in accordance with the 

TEMPERATURE  ADJUSTMENT  section  of  the 

installation manual.

 7.  Once the temperature is set, start the recirculating 

pump and allow the system to reach set tempera-

ture.

 8.  Measure the water temperature at the return pump 

and  adjust  the  aquastat  to  shut  off  the  pump 

should the return water exceed the set point by 2 

degrees F.  Set the low limit switch to restart the 

return pump when return water drops 5 degrees 

F below the set temperature.

 9.  Set the balancing valve in the full open position.
10. Shut  off  all  fixtures  and  ensure  there  is  no  draw 

on the system.  The cold inlet to the mixing valve 

should be warm.

11. Allow  the  system  to  run  in  this  condition  for  at 

least 30 minutes.

12. In some cases, an increase in water temperature  

may occur during a no draw period.  If this occurs, 

slowly  close  the  balancing  valve  until  the  water 

temperature is back to the original set temperature.

Figure 1

Typical Installation

When  used  in  a  single  temperature  

recirculating system

GuARANTEE

We guarantee the Lawler Mixing Valve to be free from 

def ects in workmanship and material, and for a pe-

riod of one year from date of purchase, will replace 

any parts found by us to be defective. We will not be 

held responsible, however, for any labor incidental 

to, or for any damages caused by defective mate-

rial. Each mixing valve is thoroughly inspected and 

tested under actual conditions at our factory.

Typical Installation

When  used  in  a  dual  temperature  

recirculating system

Figure 2

Water

Heater

Storage

Tank

Check Valve (TYP.)

To Low Temperature
Fixtures

Series 66

CW

Balancing Valve (TYP.)

Recirculating Pump

C

A

B

D

Aquastat

          TS

Heat Trap

27

 Drop

Water

Heater

Storage

Tank

Check Valve (TYP.)

To Low Temperature
Fixtures

To High Temperature
Fixtures

Series 66

CW

Balancing Valve (TYP.)

Recirculating Pumps

A

B

C

D

Aquastat

          TS

E

Heat Trap

27

 Drop

IMM000601

Отзывы: