Installation &

Maintenance Manual

M66 N

NOTICE!

Thermostatic Water Controllers will not work satisfactorily if improperly installed. 

Read these instructions carefully before installing and follow directions as outlined. 

(1)

 

B

Valve No.

 

N.P.T.

 

N.P.T.

 

C

  66-25 

3

/

4

 

3

/

4

 

10

  66-50 

3

/

4

 

1

 

10

  66-80 

1

 

1

1

/

4

 

11

  66-125 

1

1

/

4

 

1

1

/

2

 

12

3

/

4

  66-150 

1

1

/

2

 

2

 

13

1

/

4

  66-200 

2

 

2

 

15

General Description

The Series 66 water temperature controller is care-

fully assembled and tested at the factory to mix hot 

and  cold  water  to  any  desired  temperature  within 

range. The temperature of the hot water should be 

at least 20°F higher than the maximum valve setting. 

The major safety features are:
1.  Failure of cold water supply causes the hot water 

ports to reduce hot water flow.

2.  Failure of hot water supply causes the cold water 

ports to reduce cold water flow.

3.  Failure  of  the  thermostat  allows  both  ports  to 

reduce flow of hot and cold water.

At  each  inlet  of  the  controller  is  a  union  end  stop 

and check valve with removable strainer. Stop and 

check valves prevent water from bypassing between 

the  hot  and  cold  water  supply  lines.  These  valves 

should be fully open when in operation.

Maximum Inlet Conditions

Pressure: 125 psi

Temperature: 200°F

Maintenance

The controller should be checked periodically and, 

if needed, cleaned as outlined in “INSPECTION and 

CLEANING VALVE.” To test for proper setting and 

operation - proceed as follows:
1.  Turn on full hot and cold water to the valve. The 

mixing  valve  should  deliver  water  at  the  outlet 

temperature  stamped  on  the  label.  Standard 

setting is 110°F. If the outlet temperature is differ-

ent than that shown on the label, readjust valve

Series 66

 

according  to  “TEMPERATURE  ADJUSTMENT” 

procedure on page 2.

2.  If  after  adjusting  the  outlet  temperature  the  

water  stays  below  the  set  temperature,  see 

“CHECKING  COLD  WATER  SHUT-OFF.”  If  the 

temperature  stays  above  the  set  temperature, 

see “CHECKING HOT WATER SHUT-OFF.”

Caution:

  When  maintaining  and  adjusting  the 

mixing valve, all fixtures should be isolated from 

use.     Lawler Manufacturing Co., Inc. recommends 

that you work safely at all times and in a manner 

consistent with the OSHA Lock/Tagout standard, 

29 CFR 1910.147 and other applicable standards.

CAPACITIES

 

Pressure Drop PSI 

10  20  30 

45  60 

80

 

Valve Number 

Capacity-GPM

 

66-25

 

12  17  21  25  28  32

 

66-50

 

18  25  34  41  50  57  65

 

66-80

 

28  39  54  66  80  91  103

 

66-125

 

43  60  85  103  125  144  165

 

66-150

 

52  72  100  124  150  174  193

 

66-200

 

64  96  133  165  200  230  265

Checking Cold Water Shut-Off

Turn on full hot and cold water supply to the valve, 

then  shut  off  the  hot  water  stop  and  check  valve 

only. Cold water should flow through the controller 

momentarily then be reduced to a negligible amount. 
Failure to do so indicates that:

a. Plunger  is  sticking  and  requires  cleaning  or 

replacement. 

www.lawlervalve.com

       ASSE 1017 Approved

B

C

A

A

5330 East 25

th

 Street

Indianapolis, Indiana 46218

Phone (317) 261-1212

Fax (317) 261-1208

C

®

U P C

Certified to  

CSA B125.3