background image

Thermostatic Shower Valve Cut-away

Series 4000 cut away

1

2

5

22

6

21

4

8

20

12

15

16

17

18
19

11

10

14

13

7

9

Checking the Thermostat

If cold seat #9 on thermostat is worn or deeply indented, 

remove it and replace with a new one. If there is a question 

as to the thermostat being good, hold thermostat under 

cold water faucet and insert an eraser capped pencil into 

the center of thermostat. Make a reference mark where 

pencil protrudes from the thermostat. Now place the entire 

thermostat into hot water, approximately 125°F, for about 

one minute. Remove thermostat from water, examine the 

reference mark on pencil again. At this temperature, it 

should extend out from former position about 1/8”. If it does 

not, a new thermostat should be installed.

CAUTION: Extreme care should be exercised when 

placing thermostat in and out of hot water.

Checking Piston and Liner

Remove piston assembly #12 from valve. Check the piston 

assembly and liner #16 for cleanliness and excessive wear. 

Check hot disc #10 for wear. Replace all worn parts.

Note:

 Liner #16 can be removed with a:

3/8” hex wrench for med & high flow 1/2” valves,  

5/8” hex wrench for 3/4” valves.
Before reassembling the valve, thoroughly flush out with water.
Use only genuine factory parts for replacement of seat 

washers; thickness will affect the operation of the mixing 

valve.

When in Need of Information

When writing the factory or one of its representatives 

in regard to a mixing valve, be sure to give the number 

appearing on the name plate fastened to the dome.

Repair Kit

Valves can be completely rebuilt in a matter of minutes 

without removal from the line by installing a repair kit.

WARNING: This product contains chemicals known 

to the State of California to cause cancer and birth 

defects or other reproductive harm.
(Installer: California law requires that this warning 

be given to the consumer.)
For more information: www.oehha.org/prop65

Отзывы: