- 29 -
SETPOINT PROGRAMMING
From the weight display, press MENU to access the setpoint setting.
MENU/ENTER: to enter a menu/confirm the data entry.
▲
: to modify the displayed figure or menu item.
◄
: to select a new figure or modify the displayed menu item.
ESC: to cancel and return to the previous menu.
-
: if the E/EC option is connected, it is possible to set 12 groups (classes) of different
values for the setpoint; otherwise it is possible to set only the first class. Valid values for relays
switching are selected by the E/EC position.
-
(from 0 to max full scale; default: 0): Setpoint; relay switching occurs when the weight
exceed the value set in this parameter. The type of switching is settable (see section
OUTPUTS
AND INPUTS CONFIGURATION
).
-
(from 0 to max full scale; default: 0): Hysteresis, value to be subtracted from the setpoint
to obtain contact switching for decreasing weight. For example with a setpoint at 100 and
hysteresis at 10, the switching occurs at 90 for decreasing weight.
These values are set to zero if the calibration is changed significantly (see sections
THEORETICAL CALIBRATION
and
REAL CALIBRATION (WITH SAMPLE WEIGHTS)
).
…
…
…