Interval
Maintenance work
daily
Inspection of the drain plug by visual inspection from the outside
monthly
Inspection of the external hoses for material fatigue
Cleaning of the condenser
(only air-cooled devices)
Cleaning of the water filter
(only for water-cooled devices)
quarterly
Decalcification of the cooling water circuit (a shorter interval must be selected depending
on water hardness and operating time)
(only for water-cooled devices)
half-yearly
Inspection of the heat transfer liquid
7.3
Cleaning the device
Personnel:
Operating personnel
WARNING!
Ingress of cleaning agents in the device
Electric shock
Use a moist cloth for cleaning.
Also note the following:
Only clean the control panel with water and detergent. Do not
use acetone or solvents. The consequence would be perma-
nent damage of the plastic surfaces.
7.4
Cleaning air-cooled condenser
Personnel:
Operating personnel
1.
Switch off the device.
2.
Remove the front cover by holding underneath with both
hands and pulling the grating to the front. Remove the front
cover slowly and carefully to prevent damage.
3.
Brush off or vacuum the condenser.
4.
Replace the front cover carefully.
Maintenance
Microcool
51
Содержание MC 1200