Alpha
37 / 54
8.2.2
Testing the heat transfer liquid
If the heat transfer liquid becomes contaminated, it has to be replaced (
If required, the heat carrier should be checked for capability for use (for example when changing the method of opera-
tion), or at least half-yearly. Further use of the heat carrier is only permissible if the inspection indicates this.
The test of the heat transfer liquid should takes place according to DIN 51529; Testing and assessment of used heat transfer media.
Source: VDI 3033; DIN 51529.
8.2.3
Maintenance of the refrigeration unit
Condenser cleaning
The refrigeration unit operates largely without mainte-
nance.
Depending on the ambient dust conditions and the operat-
ing time, any dust on the heat exchanger (condenser)
must be removed at intervals of 2 weeks or longer.
This is done after taking off the front grille. Brush off the
condenser and if necessary blow through with compressed
air.
8.3
Note on repair
If you need to send in a unit for repair, it is essential to first contact the LAUDA Service (
If the equipment has to be returned to the factory, please ensure that it is packed carefully and
properly. LAUDA accepts no responsibility for damage due to unsatisfactory packing.
8.4
Disposal information
The following applies to Europe: The disposal of the device is regulated by EU Directive 2012/19/EU
(WEEE Waste of Electrical and Electronic Equipment).
Содержание Alpha
Страница 2: ......
Страница 4: ......
Страница 14: ...14 54 Alpha 09 2020 j 1 Control head with clamp 2 Bath vessel 3 Four mounting feet 1 2 3 ...
Страница 16: ...16 54 Alpha 09 2020 j 1 Mains cable 2 Rating label 3 Cooler cable 4 Bath drain nozzle 1 2 3 4 ...
Страница 47: ...09 2020 j Alpha 47 54 Cooling characteristics Alpha RA 8 RA 12 and RA 24 230 V 230 V ...
Страница 51: ...09 2020 j Alpha 51 54 intentionally left blank ...
Страница 52: ...52 54 Alpha 09 2020 j intentionally left blank ...
Страница 54: ...54 54 Alpha 08 2020 i ...
Страница 55: ......