6. Connect the Active, Neutral and Earth cables as per diagram below.
7. Push the socket back into the Main Body until it clips in.
8. Screw the Pressure Ring back in to form a tight seal.
9. Plug into PV Edge.
To disconnect the plug, simply push the clip in and unplug.
Note: The clip section can be completely taken out if a lockable connector
is not desired.
N
L
E
Neutral
Active
Earth
Socket
15
FAULT FINDING
HELPFUL HINTS
Should the Inverter appear to be malfunctioning we suggest the following to
eliminate any external problems.
Turn the Inverter OFF by switching the DC & external AC Circuit
Breakers OFF. Leave OFF for 60 seconds.
Reconnect the DC Solar Input by switching DC breaker ON. All lights
on the Inverter should come ON for 1 second at power up and then go
OFF. The 75% light should remain ON to indicate the Solar Input is
available. Solar Input voltage needs to be above the automatic turn ON
voltage, see pg 18, for the light to turn ON. If the light does not
illuminate check Solar Input for correct operation.
Next reconnect the AC grid by switching the external AC breaker ON.
After 20 seconds the 75% light should begin flashing to indicate Inverter
reconnecting to the AC grid. The light will flash for 60 seconds while the
PV Edge checks that the mains voltage and frequency are stable.
Should the light not begin flashing check if the AC grid is present.
After the 75% light stops flashing the Inverter will begin feeding power
into the AC Grid.
!
!
!
!
!
!
!
!
Make certain that you understand the operation of the Inverter.
Remember that it has automatic reconnection to the AC grid.
Make sure leads and terminals are not corroded, loose or faulty in any
way.
Make sure Circuit Breakers or switches are reset properly. If unsure
switch OFF and ON again.
6