3
DC WIRING
Check solar array does not exceed inverter’s maximum voltage rating!
If other sources of DC input are required e.g wind turbines, micro hydro
turbines etc, a battery bank or Latronics Turbine Controller (see pg 9) will
be required with the Maximum Power Point Tracking (MPPT) disabled
(see pg 13).
The DC input voltage is stated on the PV Edge compliance label and the
technical specifications sheet within this manual. Check that the input
voltage is within the required limits and does not exceed the maximum
limit (see pg 18).
Recommended cable size for the DC Input is 6sqmm with an insulation
rating of 0.6/1KV.
The Inverter is fitted with DC circuit breakers for the positive and
negative DC Input connections.
Ensure the DC breakers are switched OFF when connecting or
disconnecting the DC leads.
The PV Edge inverter is suitable for use with solar arrays that require positive
or negative earthing. Due to the inverter’s galvanic isolation between AC and
DC inputs no additional modifications are required. Simply connect the
positive or negative of the solar array to the system earth.
Observe Polarity.
* The inverter is designed to operate with a 48V solar panel array
(PVE1200) or 96V solar panel array (PVE2500).
* A 48V solar array will have an open circuit panel voltage of about 87Vdc.
* A 96V solar array will have an open circuit panel voltage of about 174Vdc.
*
*
*
*
*
*
POSITIVE/NEGATIVE EARTHING
18
TECHNICAL SPECIFICATIONS
Maximum DC
1200W
2500W
Maximum DC Input Current
22A
22A
Maximum DC Input Voltage
100V
200V
Maximum Power Point
54VDC - 100VDC
Tracking Range
Automatic Turn ON
70VDC
140VDC
Automatic Turn
Starting Operation
10W
10W
Number of Modules
4x 12V modules or
8 x 12V modules
Per String
2 X 24V modules
4 X 24V modules
Reverse Polarity
Protection
(MPPT - ON)
Input Power
108VDC - 200VDC
ON
54VDC
108VDC
Short Circuit Diode Across
Short Circuit Diode Across
DC Input Terminals
DC Input Terminals
Output Power
1000W cont. (1100W Max)
2100W cont. (2200W Max)
Output Voltage Range
205 -265 Vac
205- 265 Vac
Output Frequency
50Hz tol/- 1Hz
50Hz tol/- 1Hz
Peak Efficiency
93 %
93 %
Night Time Power
NIL Automatically
NIL Automatically
Consumption
Disconnects from AC Grid
Disconnects from AC Grid
Input/Output Isolation
3500V via Toroidal
3500V via Toroidal
Transformer
Transformer
Operating Temperature
- 10 C to 50 C
- 10 C to 50 C
Anti islanding Protection
Over/under voltage
Over/under voltage
Over/under frequency
Over/under frequency
Active phase shift
Active phase shift
Status Indicators
Output power in 25% Increments
Output power in 25% Increments
Grid Monitoring - Stability check
Grid Monitoring - Stability check
Solar Input ON
Solar Input ON
Grid Fault
Grid Fault
Overload
Overload
Total Energy Output kWh
Total Energy Output kWh
Wall Mount Enclosure
Powder Coated Aluminum
Powder Coated Aluminum
Dimensions
330mm x 296mm x 150mm
370mm x 386mm x 180mm
Weight
11 kg
22 kg
Connections
Hardwire Junction Box
Hardwire Junction Box
Warranty
3 years / Upgradeable 5 years
3 years / Upgradeable 5 years
CE, C-Tick
CE, C-Tick
A 3100, AS4777
A 3100, AS4777
E 55014
E 55014
Certificate of Suitability
Certificate of Suitability
(MPPT - OFF)
o
o
o
o
H
W
D
H
W
D
S
S
N
N
Output Data
General Data
Standards