background image

13

For each STRATA_HEAT™ Wire loose heating cable you install, you will have 1 unheated lead running from the floor to the thermostat’s 

electric connection. The joint connecting the unheated lead to the heating cable must be at least 2 inches (51 mm) from the wall and 

placed in a position to be covered by a thinset/adhesive under the final floor covering. THIS JOINT SECTION MUST NEVER BE PLACED IN 

THE DRYWALL.
It may be necessary to chisel out short channels in the subfloor to minimize the increased height presented by the floor probe and the 

unheated lead.
Neither the unheated lead nor sensor wire must cross, or come into contact with the heating element. Bear in mind that you will need to 

make provisions for drawing the unheated lead and sensor wire up through the conduit to the control box.

NOTE:

 The leads must be protected where they leave the floor, by rigid metal conduit, intermediate metal conduit, rigid non metallic 

conduit, electrical metallic tubing or by other approved means. 
The installation of electrical systems presents risks of fire and electrical shock which can result in personal injury. Caution should always 

be taken to guard against each such risk. All electrical connections should be carried out by a qualified electrician in accordance with the 

National Electrical Code and all local Codes. For installations in Canada, refer to sections 12 and 62 of the CEC.
The STRATA_HEAT Wire loose heating cables 

MUST

 be connected to the electrical system through a Ground Fault Circuit Interrupter 

(“GFCI”). If you are not using a thermostat with a built in GFCI, ensure that the branch circuits that supply your panels are GFCI-

protected, or, if possible, a dedicated GFCI is incorporated in each circuit supplying your panels. This requirement is critical to the safe 

operation of your STRATA_HEAT Wire loose heating cables.

ELECTRICAL PROVISIONS 

ALWAYS

 use listed conduit, fittings 

and other components. 

Conduit to power source 

Electrical box for connection to the 

thermostat 

Conduit for heating cable 

cold lead. 

Conduit for floor sensor

Heating cable 

Floor Sensor 

Содержание STRATA_HEAT 0802-0017-2

Страница 1: ...al before attempting to install your STRATA_HEAT Wire Incorrect installation could damage the STRATA_HEAT Wire and will invalidate the warranty Globally Proven Construction Solutions Globally Proven C...

Страница 2: ...l Insulation 8 Floor Coverings 8 Subfloor Preparation 9 Controlling Your System 10 Wiring Diagram 120V 11 Wiring Diagram 240V 12 Electrical Provisions 13 Testing the System 14 Planning Your Installati...

Страница 3: ...inal outer jacket of PVC is given to make it sturdier and provide corrosion protection The heating cable is terminated at one end with a 10 3 1 m cold lead The conductor cores and ground braid are fac...

Страница 4: ...2 365 111 3 73 110 147 61 91 122 0802 0398 2 398 121 3 80 120 160 66 99 133 0802 0083 4 83 25 3 17 25 33 14 21 28 0802 0100 4 100 30 5 20 30 40 17 25 33 0802 0133 4 133 40 5 27 40 53 22 33 44 0802 016...

Страница 5: ...nstalling the floor covering for future reference DO ensure that the STRATA_HEAT Wire is separated from other heat sources such as luminaires and chimneys DO ensure that the minimum bending radius is...

Страница 6: ...EAT Wire under permanent fixtures DON T commence installation on a mud job screed that has not been fully cured DON T use the STRATA_HEAT Wire system until you have allowed sufficient drying period fo...

Страница 7: ...9 1 STRATA_HEAT WIRE SPECIFICATIONS 3 5 89 mm Spacing 240 Volt Area ft m Model Length ft m Wattage W Amps A Resistance 25 2 32 0802 0083 4 83 25 3 335 1 4 177 2 30 2 79 0802 0100 4 100 30 5 400 1 6 14...

Страница 8: ...up to 5 hours to heat a room whereas a system with thermal insulation takes less than an hour If the LATICRETE STRATA_HEAT Wire is being installed onto a concrete base it is highly recommended that a...

Страница 9: ...be applied and allowed to cure If the cable is being fitted to a solid floor it is essential that the concrete slab has been allowed to cure If using the HYDRO BAN Boards use a suitable cement based...

Страница 10: ...Wire has a maximum resistive load of 15 Amps Please refer to the table on page 7 to calculate the amperage load for your particular system For smaller areas you may be able to utilize an existing cir...

Страница 11: ...11 WIRING DIAGRAM 120V...

Страница 12: ...12 WIRING DIAGRAM 240V...

Страница 13: ...electrical metallic tubing or by other approved means The installation of electrical systems presents risks of fire and electrical shock which can result in personal injury Caution should always be ta...

Страница 14: ...circuit Place one probe on the black wire Place the other probe on the yellow red wire for 240V Resistance can vary significantly depending on the ambient temperature and an allowance of 5 from the no...

Страница 15: ...rovisions to ensure proper spacing of the cable The fixing guides included in the kit are 12 305 mm long with 1 25 mm spacing guides The perimeter STRATA_HEAT Spacing Strips should be installed a mini...

Страница 16: ...as this may damage both the factory joint and or the heating element within Secure the joint to the subfloor using duct tape Do NOT completely cover the joint in tape as this may create air pockets r...

Страница 17: ...floor probe into the channels and secure with fixing tape NOTE Do NOT run the cold lead wires and the floor sensor in the same conduit Installing the STRATA_HEAT Thermostat Instructions for the fitti...

Страница 18: ...layers is 3 8 9 5 mm of thinset or adhesive When deciding between the single layer or the double layer method you should consider the following We do NOT recommend the single layer method if you will...

Страница 19: ...s Now Install the STRATA_HEAT Wire into the gap which was created by the sleepers Carefully return the cold tail lead to the junction box or the STRATA_HEAT Thermostat alongside the STRATA_HEAT Wire a...

Страница 20: ...r Energy consumption will vary depending on user preferences For lower energy consumption set the STRATA_HEAT Thermostat to optimum temperature setting Energy consumption can be minimized by turning t...

Страница 21: ...er or LATICRETE You will need to locate the model information for the heater either on the product labels you kept or based on an invoice While incorrect grounding is the main cause for breaker trippi...

Страница 22: ...22 NOTES...

Страница 23: ...end user STRATA_HEAT Wire model number Resistance ohms Insulation Resistance M ohms Before During After Before During After Installation Address Date of Installation Electricians Details Name Signatu...

Страница 24: ...24 FLOOR PLAN...

Страница 25: ...your project with confidence n Customizable warranties are available to suit your specific project requirements CERTIFICATIONS LATICRETE materials are certified by independent laboratories throughout...

Страница 26: ...26 NOTES...

Страница 27: ......

Страница 28: ...ICRETE Park North Bethany CT 06524 3423 USA l 1 800 243 4788 l 1 203 393 0010 l www laticrete com 2017 LATICRETE International Inc All trademarks shown are the intellectual properties of their respect...

Отзывы: