manualshive.com logo in svg
background image

 

Larson Electronics LLC     www.LarsonElectronics.com     [email protected]

 

9419 E US HWY 175, Kemp, TX 75143 - P: (800) 369-6671 - F: (903) 498-3364  

CHAIN MOUNTING 

This LED luminaire has four ¼-20 UNC-2B threaded holes located on the back of the luminaire for chain 
mounting. 

1.

 

Thread the four eye bolts (supplied) into the ¼ - 20 UNC-2B threaded holes on the back of the 
luminaire housing.  

2.

 

Assemble/attach the chain assemblies to the eye bolts. One chain assembly per side is provided 
for the luminaire housing. 

WIRING

 

WARNING: 

The luminaire must be grounded as required by the National Electrical Code (Paragraph 

410-21 and Article 250) or Canada Electric Code (Rule 30-500 and Section 10). Verify that the ground 
continuity has been established by using an OHM meter to other suitable testing equipment before 
energizing the luminaire. Failure to properly ground the luminaire will create an electric shock hazard, 
which can cause serious injury or death.

 

1.

 

Open the luminaire by loosening the four captive screws. Allow the cover to swing open, 
exposing the wiring compartment.  

2.

 

A. Wiring with Cable 

1.

 

Strip the cable outer jacket as required 

2.

 

Insert the cable through the conduit entry (with appropriate fitting attached) to the 
luminaire wiring compartment. 

B. Wiring with Individual Conductor Wire  

1.

 

Run conductors down through the conduit to the luminaire wiring compartment. 

Note:

 See the product nameplate for supply wire requirements. The terminal block can 

accept 24-10 AWG wire. Use the appropriate wire gauge based on the application. 

3.

 

Strip the individual conductors to bare wire and insert then into the proper terminal block 
connections. The connection points are identified on the terminal block as:                                      
“L” = Line, “N” = Neutral, “G” = Ground.  Tighten down the terminal block screws onto the wire. 

4.

 

Once the terminal block is wired to incoming power, close the luminaire cover and tighten the 
four captive screws.  

5.

 

Close all unused conduit entries with conduit plugs (2 Supplied). Make sure to tighten all unused 
close-up plugs to 400 in. –lb. after applying TLNC4 grease. TLNC4 grease shall be applied in 3 
lines, spaced approximately 120° apart, perpendicular to the threads. 

6.

 

Power can now be applied to the luminaire. 

Отзывы: