MAINTENANCE
Before removing the cover from any such device for inspection or maintenance, the power supply circuit
must be OFF.
WARNING:
To prevent risk of explosion, hammers and prying tools must not be used to remove covers
off enclosures. Damage to the explosion proof flat machined surfaces on cover and enclosure may
result. Handle covers carefully. Do not place them on surfaces that might damage or scratch the flat
machined surfaces.
Before replacing the cover, after it has once been removed, the flat ground joint surfaces must be
cleaned as described in step 3 under installation.
WARNING:
To prevent risk of explosion, replace devices if the flat machined surface is damaged,
scratched, dented, or corroded. Field rework of flat machined surfaces is not possible.
CAUTION:
Use 12 AWG copper conductors only. Insert the
bare wire conductor(s) under the terminal clamp and securely
tighten the screw(s). Note: Do not exceed 35 in-lbs. of torque.
THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS.