background image

 

14 

The Fan and Light buttons will be illuminated indicating power is going to the fan(s) and light(s). The system will 
start the fan(s) at minimum speed of 30% and will increase up to 100% as the cooking load/temperature 
increases until the Exhaust fan(s) are at 100%. The MUA fan(s) will adjust output independent of the Exhaust 
fan(s) and maintain building balance. The fan(s) and light(s) will continue to operate when in Auto Run Mode until 
all of the following shut down conditions are met: the factory set 30 minute Initial Safety Timer has elapsed, the 
cooking equipment has been turned off, the sensor(s) do not detect a temperature above the factory pre-set Low 
End Turn Off (88° F) for 3-5 minutes.  
 
The system may also be manually operated by pressing the Light and Fan buttons; however, the system will enter 
“Auto Mode” if the system detects a temperature rise associated with cooking operations. If the system changes 
from “Manual Mode” to “Auto Mode” because of a temperature rise, it will shut down automatically once the 
system no longer detects a cooking operation. 

Note:

 

The system will not shut down manually or 

automatically until all the previously mentioned shut down conditions have been met

. For multiple hood 

systems, the warmest sensor must cool to the factory set point of 88° F before automatic de-activation can take 
place. 
 
 

WARNING:

 It is not recommended to adjust this system except in extreme cases. Please consult factory 

before attempting any adjustments.

 

 
 
The microprocessor-based controller contains 4 basic adjustments: 
 
 

 

 
 

Note: Advanced settings are password protected in the menu of the touch screen display. If your system 
is not operating properly, do not attempt adjusting controller before contacting customer support at 800-
322-4036. 

 
The AFC-DCV system is designed to shut down the light(s) and MUA fan(s) and continue to run the Exhaust 
fan(s) in the event of fire and activate two Normally Open/Normally Closed (NO/NC) spare dry contacts (may be 
used for building alarm, horn strobe, etc.). Terminal STH (Shunt Trip Hot) will also provide 120 VAC for shunt trip 
breaker in fire mode. 

 

Maintenance 

 
 

CAUTION! More than one disconnect switch may be required to de-energize the equipment before 
servicing. Ensure all power sources have been disconnected before installing or servicing the system. 
VFD(s) can be holding stored energy when main supply has been switched off. DO NOT touch power 
connections immediately. Check power terminals for isolation from supply.

   

 
 

 

The Control Box door should be securely closed after opening to avoid tampering or electrical shock. 

 
 

 

The Control Box is a type1 electrical enclosure and is not watertight.  Do not spray, soak, or submerge with 
water. Control Box should only be cleaned with a mild cleaner and damp cloth. 

 

 

Hood temperature sensor(s) should be cleaned often to prevent grease build up and ensure a quick response 
to temperature changes. Sensor(s) should be cleaned with a mild cleaner to remove grease. 

Содержание AFC-DCV

Страница 1: ...all mount control box includes the following Wall mounted 18 x 26 x 8 stainless steel enclosure with hinged door and tamper resistant latch Color touch screen display mounted on enclosure door for system operation Exhaust and Make Up Air MUA fan s are interlocked If hood fire suppression system is activated the lights and MUA fan s shut down The Exhaust fan s will continue to operate at 100 Temper...

Страница 2: ...oused in an 18 x 26 x 8 stainless steel enclosure and should be secured to a fixed wall near the exhaust hood s it controls Fig 1 NOTICE The VFD s produce heat and must have proper ventilation THE AFC DCV ENCLOSURE CAN NOT BE RECESS MOUNTED Fig 1 ...

Страница 3: ...l to Control Box for fan s See wiring diagram F 3 Phase wired from Control Box to fan s See wiring diagram G tubing from pressure sensor in control box to outdoor pick up Note If unable to install tubing to pressure sensor pick up contact technical support at 800 322 4036 Note If Tempered MUA is provided the tempering lock out connection must be made from the Control Box to the tempered unit on te...

Страница 4: ...nting sensor between a light and the end of the hood may be required on shorter hoods CAUTION If sensor is located too close to a light fixture the heat generated could activate the system The sensor s should be centered between lights Wiring Instructions The Larkin AFC DCV components are all prewired The field wiring required to connect the Control Box to the hood s and breaker panel should be ma...

Страница 5: ...pered MUA unit a tempering lock out connection must be connected to the Tempered MUA unit from the control box or the unit may not operate properly see Tempered MUA Unit wiring diagram connections from R and W1 Pg 8 Field Wiring Requirements for Control Panel Control Circuit Field wire 120 VAC 1 Phase 15 AMP circuit to the Control Panel terminals Control Hot CH Control Neutral CN and Ground GND fr...

Страница 6: ...nnected to the terminal strip and the dip switch for that sensor is in the off position the auto activation and DCV functions of the system will not be active for that sensor Micro Switch The Larkin AFC DCV requires a Fire Suppression System Micro Switch connection The Micro Switch should be field wired from the Fire Suppression System to the Control Box connecting the Common C lead from the Micro...

Страница 7: ...Connect tubing to the Outdoor connection the open port on the pressure sensor The Indoor connection should already have tubing connected to the Indoor Pick Up in the top of the Control Box Note This is required for differential building pressure control If unable to install tubing from the Outdoor Pick Up to the Pressure Sensor in the Control Box contact technical support at 800 322 4036 Fan Input...

Страница 8: ...he Control Box to the Tempered MUA unit If this connection is not made the unit may not operate properly Tempered MUA units may not operate properly below a 50 volume This connection allows the Control Box to lock out the heat cool function of the unit when the turn down is below 50 When a Larkin Industries Tempered MUA unit is provided use low voltage wiring from terminal R and W1 in the Control ...

Страница 9: ...closed connections C2 NC2 NO2 and C3 NC3 NO3 Contacts are provided for activation of building alarm horn strobe etc Up to 120V 15A power may be connected to C2 and or C3 for activation or de activation of auxiliary controls in Fire Mode The NC2 and NO2 terminals will have whatever voltage has been connected to C2 The NC3 and NO3 terminals will have whatever voltage has been connected to C3 In Fire...

Страница 10: ...hunt trip control voltage from the Control Box terminal Shunt Trip Hot STH to the trip terminals on the shunt trip breaker a neutral may be supplied from breaker panel This will provide 120V 1 PH power to trip the breaker in Fire Mode See Pg 9 If a Tempered MUA unit is used connections from the control box to the Tempered MUA unit must be made to terminals R and W1 for control of tempering lock ou...

Страница 11: ...ssure Hood sensor temperature on the display should be approximately the same as the room temperature Check the rotation of the fan s Note The exhaust fan s will exhaust some air while rotating in reverse Checking rotation may be accomplished in two different ways 1 you may check the direction arrow on the fan s or 2 depress the 100 Override button on the display and monitor the motor amperage dis...

Страница 12: ...eturn to return to the previous menu Adjusting Max Speed The max Exhaust speed will need to be adjusted if the MUA cannot maintain correct pressure Connect the keypad to the VFD controlling the fan to be adjusted Using the above instructions navigate to parameter P430 03 This will display 60HZ If the fan speed needs to be adjusted depress the Scroll Down button to lower the max HTZ of the fan Depr...

Страница 13: ...or multiple hood systems when any hood sensor s detects a temperature rise the fan s and light s will automatically energize for all hoods connected to that Control Box Note Allow the system to continue operating after the automatic activation to perform fire system test described below 3 For this portion of the test the system should still be operating in automatic mode described above The system...

Страница 14: ...st this system except in extreme cases Please consult factory before attempting any adjustments The microprocessor based controller contains 4 basic adjustments Note Advanced settings are password protected in the menu of the touch screen display If your system is not operating properly do not attempt adjusting controller before contacting customer support at 800 322 4036 The AFC DCV system is des...

Страница 15: ...15 See Pg 6 ...

Отзывы: