background image

 

10 

Installation Check List 

 

Is Control Box mounted next to the exhaust hood(s) it controls (See Pg. 2)? 

 

Are two separate circuits (120VAC 15AMP control and 120VAC 15AMP hood lights) connected from breaker panel 
to control box per NEC (See Pg. 5)? 
 
Are hood lights connected from the Control Box to the hood light junction box per NEC (See Pg. 5)? 
 
Are hood sensor(s) connected from hood(s) to Control Box (One sensor per hood or hood section)? Check dip 
switch position (See page 6).  

 

Is there a Micro-Switch wired to the control box from the fire system (See Pg. 6)? 

Warning: Do not apply voltage 

through Micro-Switch. This WILL cause damage to the control board.  

 

 
Is input power of proper Phase and Voltage from the breaker panel connected to each VFD terminals L1, L2, and 
L3 per NEC in the Control Box (See Pg. 7)? 
 
Is the ¼” tubing (provided) connected to the Outdoor Pick-Up, routed through conduit (as identified on Pg. 7) to the 
Control Box and connected to the “Outdoor” connection (the open port) on the pressure sensor in the Control Box 
(See Pg. 7)? Is Outdoor Pick-Up installed upright (removable cover facing up)?

 Note: This is required for 

differential building pressure control. If unable to install tubing from the Outdoor Pick-Up to the Pressure 
Sensor in the Control Box, contact technical support at 800-322-4036.

 

 
Is output power from VFD(s) terminals U, V, and W in the Control Box connected to the proper fan(s) on the roof 
(Exhaust to Exhaust, Supply to Supply) per NEC (See Pg. 8)? 

Notice:

 

Regardless of input power VFD(s) will 

only output 3 PH power. 

 

 
 

Optional Equipment: 

 
If a shunt trip breaker is required, connect the shunt trip control voltage from the Control Box terminal Shunt Trip 
Hot (STH) to the trip terminals on the shunt trip breaker (a neutral may be supplied from breaker panel). This will 
provide 120V 1 PH power to trip the breaker in Fire Mode (See Pg. 9). 
 
If a Tempered MUA unit is used, connections from the control box to the Tempered MUA unit must be made to 
terminals R and W1 for control of tempering lock-out. Jumper from terminal R and W1 must be removed when 
making this connection (See Pg. 8). 
 
If Wiring for building fire alarm, strobe horn, etc. is required field wire to the proper Common, Normally Closed or 
Normally Open terminals in the control box. Up to 120V 15A power may be connected to C2 and/or C3 for 
activation or de-activation of auxiliary controls in Fire Mode. The NC2 and NO2 terminals will have whatever 
voltage has been connected to C2. The NC3 and NO3 terminals will have whatever voltage has been connected 
C3. In Fire Mode, NC2 and NC3 contacts will open and no longer have the connected power through these 
terminals for “Off in Fire”. At the same time, NO2 and NO3 will close in Fire Mode supplying the connected voltage 
to those terminals for “On in Fire” (See Pg. 9).  

 

  

For technical support contact Larkin Industries, Inc. 1-800-322-4036

 

 
 

System Startup 

 

Turn on all breakers that power the fan VFD(s), Control Box power, hood lights. The color touch screen display 
should power on. If display needs calibration, simply touch the dots on the screen. Check for proper voltage at all 
terminals with fan control off. Each VFD should have a blue blinking “Ready” light with “STOP” displayed on the 
keypad. Keypad should be moved from one VFD to another to ensure all VFDs are in “Stop” mode. Cooking 
equipment should be off, fan(s) should not be operating and “System Off” should be on the display.  

Содержание AFC-DCV

Страница 1: ...all mount control box includes the following Wall mounted 18 x 26 x 8 stainless steel enclosure with hinged door and tamper resistant latch Color touch screen display mounted on enclosure door for system operation Exhaust and Make Up Air MUA fan s are interlocked If hood fire suppression system is activated the lights and MUA fan s shut down The Exhaust fan s will continue to operate at 100 Temper...

Страница 2: ...oused in an 18 x 26 x 8 stainless steel enclosure and should be secured to a fixed wall near the exhaust hood s it controls Fig 1 NOTICE The VFD s produce heat and must have proper ventilation THE AFC DCV ENCLOSURE CAN NOT BE RECESS MOUNTED Fig 1 ...

Страница 3: ...l to Control Box for fan s See wiring diagram F 3 Phase wired from Control Box to fan s See wiring diagram G tubing from pressure sensor in control box to outdoor pick up Note If unable to install tubing to pressure sensor pick up contact technical support at 800 322 4036 Note If Tempered MUA is provided the tempering lock out connection must be made from the Control Box to the tempered unit on te...

Страница 4: ...nting sensor between a light and the end of the hood may be required on shorter hoods CAUTION If sensor is located too close to a light fixture the heat generated could activate the system The sensor s should be centered between lights Wiring Instructions The Larkin AFC DCV components are all prewired The field wiring required to connect the Control Box to the hood s and breaker panel should be ma...

Страница 5: ...pered MUA unit a tempering lock out connection must be connected to the Tempered MUA unit from the control box or the unit may not operate properly see Tempered MUA Unit wiring diagram connections from R and W1 Pg 8 Field Wiring Requirements for Control Panel Control Circuit Field wire 120 VAC 1 Phase 15 AMP circuit to the Control Panel terminals Control Hot CH Control Neutral CN and Ground GND fr...

Страница 6: ...nnected to the terminal strip and the dip switch for that sensor is in the off position the auto activation and DCV functions of the system will not be active for that sensor Micro Switch The Larkin AFC DCV requires a Fire Suppression System Micro Switch connection The Micro Switch should be field wired from the Fire Suppression System to the Control Box connecting the Common C lead from the Micro...

Страница 7: ...Connect tubing to the Outdoor connection the open port on the pressure sensor The Indoor connection should already have tubing connected to the Indoor Pick Up in the top of the Control Box Note This is required for differential building pressure control If unable to install tubing from the Outdoor Pick Up to the Pressure Sensor in the Control Box contact technical support at 800 322 4036 Fan Input...

Страница 8: ...he Control Box to the Tempered MUA unit If this connection is not made the unit may not operate properly Tempered MUA units may not operate properly below a 50 volume This connection allows the Control Box to lock out the heat cool function of the unit when the turn down is below 50 When a Larkin Industries Tempered MUA unit is provided use low voltage wiring from terminal R and W1 in the Control ...

Страница 9: ...closed connections C2 NC2 NO2 and C3 NC3 NO3 Contacts are provided for activation of building alarm horn strobe etc Up to 120V 15A power may be connected to C2 and or C3 for activation or de activation of auxiliary controls in Fire Mode The NC2 and NO2 terminals will have whatever voltage has been connected to C2 The NC3 and NO3 terminals will have whatever voltage has been connected to C3 In Fire...

Страница 10: ...hunt trip control voltage from the Control Box terminal Shunt Trip Hot STH to the trip terminals on the shunt trip breaker a neutral may be supplied from breaker panel This will provide 120V 1 PH power to trip the breaker in Fire Mode See Pg 9 If a Tempered MUA unit is used connections from the control box to the Tempered MUA unit must be made to terminals R and W1 for control of tempering lock ou...

Страница 11: ...ssure Hood sensor temperature on the display should be approximately the same as the room temperature Check the rotation of the fan s Note The exhaust fan s will exhaust some air while rotating in reverse Checking rotation may be accomplished in two different ways 1 you may check the direction arrow on the fan s or 2 depress the 100 Override button on the display and monitor the motor amperage dis...

Страница 12: ...eturn to return to the previous menu Adjusting Max Speed The max Exhaust speed will need to be adjusted if the MUA cannot maintain correct pressure Connect the keypad to the VFD controlling the fan to be adjusted Using the above instructions navigate to parameter P430 03 This will display 60HZ If the fan speed needs to be adjusted depress the Scroll Down button to lower the max HTZ of the fan Depr...

Страница 13: ...or multiple hood systems when any hood sensor s detects a temperature rise the fan s and light s will automatically energize for all hoods connected to that Control Box Note Allow the system to continue operating after the automatic activation to perform fire system test described below 3 For this portion of the test the system should still be operating in automatic mode described above The system...

Страница 14: ...st this system except in extreme cases Please consult factory before attempting any adjustments The microprocessor based controller contains 4 basic adjustments Note Advanced settings are password protected in the menu of the touch screen display If your system is not operating properly do not attempt adjusting controller before contacting customer support at 800 322 4036 The AFC DCV system is des...

Страница 15: ...15 See Pg 6 ...

Отзывы: