LA-ON-RACK 6K/10K
13: Battery voltage adjustment
Interface Setting
Parameter 2:
Select “
Add
” or “
Sub
” function to adjust battery voltage
to real figure.
Parameter 3:
the voltage range is from 0V to 5.7V, the default value
is 0V.
14: Charger voltage adjustment
Interface Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust charger voltage
Parameter 3:
the voltage range is from 0V to 9.9V, the default value
is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
*We strongly suggest to use the default value (0). Any modification
should be suitable to battery specifications.
15: Output voltage adjustment
Interface Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter voltage
Parameter 3:
the voltage range is from 0V to 6.4V, the default value
is 0V.
3.8. Operating Mode/Status Description
Operating mode/status
Description
When the input voltage is within acceptable range, UPS will provide pure
and stable AC power to output. The UPS will also charge the battery at AC
mode.
AC mode
LCD display
Description
When the input voltage is within voltage regulation range and ECO mode is
enabled, UPS will bypass voltage to output for energy saving.
ECO mode
LCD display