lapara 6KR Скачать руководство пользователя страница 16

15 

 

15

LA-ON-RACK 6K/10K 

3.5. Parallel Operation 

1. Parallel system connection 

1)    Make sure all of the UPSs are parallel models, and follow the wiring refer to section 2-3.   

2)  Turn off the input and output breakers of each UPS, and turn off the battery breaker if the UPS is 

long-run model. 

3)  Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one with 

the parallel cable and share current cable, and then screw the cover back again. 

4)  Turn on the input breaker of the each UPS and measure the voltage difference between the output line1 

of each UPS with multimeter. If the voltage difference is less than 1V, it means all connections are 
correct. If the difference is larger than 1V, check if the wirings are connected correctly.   

5)  Turn on the input breakers of all UPSs in the parallel systems and turn on each UPS in turns. Make sure 

that AC mode LED or Battery mode LED displays in each UPS. Measure the output voltage of each 
UPS to check if the voltage difference is less than 2V (typical 1V) with multimeter. If the difference is 
more than 2V, please check that parallel cable or share current cable are connected well. If they are all 
connected well, maybe it’s UPS internal issue. Please contact your local distributor or service center for 
help.  

6)  Turn off each UPS in turns and after all of them transfer to Bypass mode, turn on the output breaker of 

each unit. 

7)  Turn on the UPSs in the AC mode and then the parallel system connection is complete.   

2. Add one new unit into the parallel system 

1)    You can not add one new unit into the parallel system when whole system is running. You must cut off 

the load and shutdown the system.   

2)    Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-3. 

3)    Install the new parallel system refers to the previous section. 

3. Remove one unit from the parallel system 

1)    If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load 

and shut down the system.   

2)    Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs 

will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance 
switches from “UPS” to “BPS”.    Turn off the input breakers and battery breakers.   

3)    Remove the UPS that you want. 

4)    Turn on the input breaker of the remaining UPSs and the system will transfer to Bypass mode.   

5)  Set the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back. Turn 

on the remaining UPSs and finish the parallel system connection.   

 

Warning: 

(Only for the parallel system) 

 Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance switch at 

the same position. 

 When parallel system is turned on to work through inverter, please do not operate the maintenance switch 

of any unit. 

Содержание 6KR

Страница 1: ...Online UPS 6K 10K RACK Uninterruptible Power Supply System USER MANUAL EN...

Страница 2: ...d operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all...

Страница 3: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 9 3 OPERATIONS 10 3 1 BUTTON OPERATION 10 3 2 LED INDICATORS AND LCD PANEL 10 3 3 AUDIBLE ALARM 12 3 4 SINGLE UPS OPERATION...

Страница 4: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over the...

Страница 5: ...nnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Страница 6: ...toring software CD One RS 232 cable option One USB cable One EPO plug One parallel cable only available for parallel model One share current cable only available for parallel model One battery cable o...

Страница 7: ...Cooling fan 8 External maintenance bypass switch port 9 Maintenance bypass switch 10 Input circuit breaker 11 Output receptacles connect to mission critical loads 12 Output circuit breaker for recepta...

Страница 8: ...A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for color of wires should be followed by the local electrical laws and regulations 5 Remove the...

Страница 9: ...etting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking...

Страница 10: ...timal computer system protection install UPS monitoring software to fully configure UPS shutdown Install CD or visit the website http www power software download com for the latest software version Di...

Страница 11: ...s this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key P...

Страница 12: ...level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Programmable output information Indicates that the programmable outputs are working Mode operation inf...

Страница 13: ...tery pack at ON position the step only available for long run model Then set the input breaker at ON position At this time the fan is running and the UPS supplies power to the loads via the bypass The...

Страница 14: ...ation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery vo...

Страница 15: ...g alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 11 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that th...

Страница 16: ...ter all of them transfer to Bypass mode turn on the output breaker of each unit 7 Turn on the UPSs in the AC mode and then the parallel system connection is complete 2 Add one new unit into the parall...

Страница 17: ...ves There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program 15 programs available list for parameter 1 Code Description Bypa...

Страница 18: ...utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode Settin...

Страница 19: ...0 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volta...

Страница 20: ...ens the programmable output also will be cut off automatically If it happens 3 times the programmable output will be cut off until it is manually switched on 11 Shutdown point for programmable output...

Страница 21: ...ger voltage We strongly suggest to use the default value 0 Any modification should be suitable to battery specifications 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add o...

Страница 22: ...Battery mode LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD di...

Страница 23: ...1 None Output circuit circuited 36 None High Inverter voltage 12 None Over temperature 41 None Low Inverter voltage 13 None CPU communication failure 42 None Inverter output short circuited 14 Overloa...

Страница 24: ...cked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD...

Страница 25: ...d with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery term...

Страница 26: ...er to 90 capacity 4 hours recover to 90 capacity Charging Current 2 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 2 A 10 max Long run...

Отзывы: