(ESN) that are unique for each series TF1100heat meter.
M62
RS232C communication setup
Commonly, user should select
“9600, None”
9600 is baud rate, check bit
is “None”.
M63
Analog input temperature sensor range value for heat flow
application, wiring terminals is Tin+, Tin-. Press ENTER and
use key
∧
or
∨
to input value corresponding 4mA and
20mA
M64
Analog input temperature sensor range value for heat flow
application, wiring terminals is Tout+, Tout-. Press ENTER
and use key
∧
or
∨
to input value corresponding 4mA and
20mA
M65
Setup the frequency range for the frequency output. The
biggest range is 0Hz-9999Hz. Default value is 1-1001 Hz.
M66
Setup the Low Frequency Output
Corresponding Value of Flow Rate.
This value correspond to the lowest
Frequency value entered in M65.
M67
Setup the High Frequency Output
Corresponding Value of Flow Rate.
This value correspond to the highest
Frequency value entered in M65.
Please see the *Note for wiring diagram.
M70
LCD Backlit option. User can select “Always On”, Always
Off” or “Lighting for” items, if select “Lighting for”, please
entered a second value, it indicates how many seconds the
backlight will be on.
M71
LCD contrast control. The LCD will become darker when a
small value is entered.
M72
Working timer. It can be cleared by pressing ENTER key, and
then select YES.
M73
Alarm #1 Low Value
Enter Lowest Flow Rate value that will trigger the Relay
M62
RS-232C Setup
9600, None
M66
Low FO Flow Rate
0 m3/h
M67
High FO Flow Rate
3000 m3/h