For example:

In UK, the country code is

0044

, or

+44

.

The user cell phone number is

3408888666

and has been assigned as the first user number, the simcard number

in the panel is

3408888555

.

Problem 1: Relay action but the first user haven’t received the SMS .
Solution:

Please plus the country code while you setup the

3408888666

as the first user number, means setup

00443408888666

to instead of the

3408888666

.

Problem 2: The user number can receive the Relay action message from the RTU 5024, but the RTU 5024 can
not receive the commands from the first user number.
Solution:

Please add country code to the simcard number in the RTU 5024. Means send sms commands to

003408888555

to instead of

3408888555

.

Solution 3:

When you use cell phone dial another one, what number it will be di splayed then you can set the

displayed number as dial numbers; when you use cell phone send SMS to another cell phone, what number it will
be displayed then you can set the displayed number as the first user number, just use the 00 to replace the “+”,
also, you can try the “+”.

2. All the settings are through SMS commands, please edit the below SMS commands in your cell

phone, then send to the RTU5024 Unit. The unit cannot support PIN Code Protected SIMCard.

3. You can program the GSM Gate Opener with SMS commands using your phone. It is safe to do

so because in addition to the fact that other people may not know the number of the SIM
inserted in it, we also use a Password that makes it impossible for anybody, who doesn't know it,
to access the system by chance.

4. The relay output will change the close or open status by every call in, please note it. Means the

first time call it, it will close the relay to switch on the lock, if the second call in is in the setting
time, then the unit will ignore the setting time, and open the relay, to switch off the lock or
machine.

5. Remember that commands must be

CAPITAL Lock LETTERS

. It is PWD not pwd, CAP not Cap

etc. Don't add spaces or any other character.

6. The

pwd

in the commands is means the password, when you use it, please in stand of it by the

digital number; the capital letters

PWD

is the command letter, use PWD directly.

7. If you use this model for gate open, you only need to change the password and setup the

authorized numbers

8. In some GSM operators they use different SMS parameter; the units can’t return the SMS

confirmation is normally. It is not product problem. Also, you can try to add the country code
before the number, see the below settings:

9. Please write down the Authorized number list in a paper for review in further.
10. If you want to reset the RTU5024 to factory default, then please send pwd#RESET# (The unit will

reply to Reset Success! Please Reboot your Device ) or When the RTU5024 works normally, you
can always press the RESET key beside the SIMCard for several seconds until the RUN Led always
is ON.

Содержание RTU5024

Страница 1: ...or and Door opener Open gate or garage door with a FREE call from your mobile phone Remote switching machines with a FREE call from your mobile phone GSM Gate Opener GSM Remote Switch RTU5024 User Man...

Страница 2: ...ntained in the handbook are general guidelines only and in no way are designed to supersede the instructions contained with other products We recommend that the advice of a registered electrician be s...

Страница 3: ...rejects the call from authorized number then carries out the turn ON OFF action 2 Safety Directions Safe Startup Do not use GSM SMS IR Controller when using GSM equipment is prohibited or might bring...

Страница 4: ...r 1 second quickly registering to cellular network Flash per 2 seconds Normal status OFF can not connect to SIM card or unregistered to the cellular network Relay Relay Status calling in the relay wil...

Страница 5: ...he GSM Gate Opener rejects the call from authorized number then carries out the turn ON OFF action on the first ring 2 It is no longer traditional to open the door but it is more interesting to open t...

Страница 6: ...because in addition to the fact that other people may not know the number of the SIM inserted in it we also use a Password that makes it impossible for anybody who doesn t know it to access the system...

Страница 7: ...any other character When input punctuation symbol must be under ENGLISH or DIGITAL input method Not support other input method 6 2 Setup Authorized number E g if you want to setup 13500001111 as the...

Страница 8: ...umbers can access it or Allow User Numbers can access it only 6 7 Setup the relay close time Tips The time should be in 0 9 5seconds This command is useful in case you need to keep the relay closed or...

Страница 9: ...SMS confirmation when Relay action Tips if you enable it when the relay action close or open the unit will return a SMS confirmation to you The first user number The return SMS is Relay ON Operated by...

Страница 10: ...ame The mainframe should be installed in the position that person can not get it and there with a power source as well as enough GSM signal coverage 8 Technical specifications Rated Voltage 12VDC 1 A...

Страница 11: ...If the remote control works but the Control Unit fails to send SMS texts switch the power of Control Unit off and switch it on after one minute Test this system after another minute or check the setti...

Страница 12: ...11 The End Any questions please help to contact us feel free Made by Langjushan Tech langjushan tech hotmail com 17324422003...

Отзывы: