Figure 12: Temperature sensor connection

Connect the wires according to the printed wiring diagram.

The connection is made to terminals 5/6 (warm side

temperature sensor) and 7/8 (cold side temperature

sensor).

Insert the temperature sensors into the thermowells, ball

valves or T-pieces. The temperature sensor must sit on the

bottom of the thermowell.

Seal the temperature sensors to prevent manipulation.

Close the housing cover by tightening the screw (see

chapter Torque) and press the housing cover tightly into

place.

If the LCD displays 

, you can reset this error message via

the parameterisation menu. Please refer to the service manual.

10 Commissioning

Proceed as follows when carrying out the commissioning:

Close the housing cover by tightening the screw (see

chapter Torque) and press the housing cover tightly into

place.

Slowly open the gate valves.

Check the system for leaks and vent it carefully.
The message F0 disappears after 100 s at the latest.

Check the flow and temperature indicators for plausibility.

Vent the system until the flow display [ID 000] is stable.

Attach user guards to the calculator and temperature

sensors.

Document the meter readings.
Recommendation: Reset the maximums and the absence

time. More details can be found in the T450 service manual.

11 Error messages due to incorrect installation

Note

When the system is at a standstill, these messages can also

be displayed without incorrect installation

Error "Incorrect flow direction

(negative)" Check whether the

flow direction arrows on the

volume meter correspond to

the flow direction of the

system. If the directions do not

match, rotate the volume

meter 180°.

Error "negative temperature

difference" Check whether the

temperature sensors are

correctly installed. If the

temperature sensors are not

correctly installed, swap the

installation location of the

temperature sensors.

Heat meter: Temperature

sensor in the flow pipe - pipe

with higher temperatures;

Temperature sensor in the

return pipe - pipe with lower

temperatures

Cooling meter: Temperature

sensor in the flow pipe - pipe

with lower temperatures;

Temperature sensor in the

return pipe - pipe with higher

temperatures

12 Display

The functions of the LCD are described in detail in the operating

manual included.

13 Error messages

Note

Reset the message F8 in parameterisation mode manually

or with UltraAssist. All other error messages are

automatically deleted after the error has been corrected.

The meter regularly performs a self-diagnosis and can recognise

and display various 

 errors and error messages.

Table 1:

Error code

Error

Information for

Service

Wrong flow

direction

Check flow and

installation

direction and

correct as necessary

Possibly alternating with:

Negative

temperature

difference

Check installed

position of

temperature

sensor; change if

necessary

Possibly alternating with:

No flow measurable Air in measuring

part/tube, bleed

the line (status at

delivery)

© Gyr

Subject to change without prior notice

07.02.2020

7

Содержание T450

Страница 1: ...arantees Caution Comply with the requirements for circulation water CEN TR 16911 2016 Caution The meter is only suitable for circulation water in heating systems Caution The meter is not suitable for...

Страница 2: ...ion corresponds to the return and the cold side installation location to the supply Proceed as follows to install the meter 1 Compare the installation location with the symbol on the LCD or to determi...

Страница 3: ...Press button 2 briefly to complete the change The change can be checked using the symbols or on the LCD If necessary adjust the temperature sensors according to the installation requirements 4 2 Inst...

Страница 4: ...e temperature sensors are horizontal or vertical Figure 7 Recommended installation position of cooling meters and combined heat cooling meters 5 Calculator The ambient temperature of the calculator mu...

Страница 5: ...follows to change the battery If necessary open the battery compartment cover by loosening the screw Remove the old batteries from the battery compartment Insert the battery into the battery compartm...

Страница 6: ...on Note No later than 60 seconds after installation the meter automatically detects the inserted modules and is ready for communication or pulse output 7 2 Terminal blocks 2 pin or 4 pin terminals are...

Страница 7: ...be displayed without incorrect installation Error Incorrect flow direction negative Check whether the flow direction arrows on the volume meter correspond to the flow direction of the system If the di...

Страница 8: ...necessary or Error in internal memory Change the device The measurements of the meter may no longer be used for legally calibrated billing Error code Error Information for Service F2 F3 F5 or F6 pers...

Отзывы: