Landis+Gyr 750 Скачать руководство пользователя страница 9

 

Model 750 Gas Meter 

Installation, Commissioning and Maintenance Manual

 

 

Page 9 of 17 

© Gyr  

 

17-May-2016 

Due to continuous product development the details above are subject to change without notice. Whilst Gyr has taken all reasonable 

care in reviewing the information in this document, Gyr makes no representations in respect of, gives no guarantees or undertakings in 

relation to, and to the maximum extent permitted by law, excludes all warranties in relation to, the accuracy or completeness of the information 

in this document. Prospective users of this information should make their own enquiries as to its accuracy and reliability. 

ensure  that  the  maximum  operating  pressure  of  the 
meter is not exceeded. 

When  the  meter  is  used  with  gases  high  in 
contaminants it is recommended that a suitable filter is 
installed on the inlet side of the meter. 

A  suitable  stop  valve  should  be  installed  before  the 
inlet of the meter for maintenance purposes. 

Avoid installing the meter in locations where the meter 
casing  is  in  direct  contact  with  soil  or  concrete  walls. 
Alkali in concrete as  well as other corrosive elements 
in  soil  can  cause  premature  corrosion  of  the  meter 
casing. 

3. 

Pipe Work Installation 

Ensure that installation pipe work is thoroughly clean. 
Foreign  materials  such  as  pipe  scale,  rust  flakes, 
excessive  plumbing  tape,  excessive  thread  sealant 
must be removed prior to installing the meter. 

The  gas  meter,  weighing  2.7  kg,  can  be  supported 
entirely by the meter bosses. It is typical for the meter 
to be suspended by pipe work alone. 

The  installer  shall  ensure  that  the  pipe  work 
does  not  result  in  excessive  forces  being 
applied to the meter bosses. The suitability of 

the pipe work is the responsibility of the installer. 

The gas meter should be installed as close to level as 
possible  in  order  to  ensure  accurate  operation.  The 
pipe  work  shall  be  in  line  with  the  meter  bosses  and 
not forced into position. The direction of gas flow must 
correspond to the arrow marked on the meter body. 

Hand tighten the  inlet   and outlet swivel cap.  Using a 
pipe wrench, alternate between both swivel caps nuts 
and  tighten  approximately  three  flats  (approximately 
15  -  25  Nm).  DO  NOT  OVER  TIGHTEN.  Damage  to 
the rubber gasket inside the swivel cap nut may result. 

PUTTING INTO OPERATION 

Before  turning  the  gas  on,  check  the  system  down-
stream of the meter to be sure that all connections are 
made  up  and  tight  or  that  the  downstream  valve,  if 
there is one, is closed. 

CARE  must  be  taken  to  prevent  excessive 
flows  and  high  pressure  drops  across  the 
meter. 

If CARE is not exercised when pressurising the meter 
over-speeding of the meters internal mechanism may 
result  in  internal  damage  to  the  meter.  To  prevent 
over-speeding  the  pressure  drop  across  the  meter 
should  not  exceed  125  Pa  or  (0.

5”  wc).  This  can  be 

achieved  by  pressurising  the  meter  and  the 
downstream pipe volume to appliances as slowly as is 
possible. 

To  avoid  high  differential  pressure  across  the  meter, 
open  the  upstream  and  downstream  valves  VERY 
SLOWLY to prevent any pressure surges into or out of 
the meter. 

4. 

Check For Leaks 

Check for leaks and check all connections for 
tightness. Repair all leaks as required. 

Use liquid leak detector to check for leaks at the pipe 
connections. 

5. 

Turn On Appliances 

All  air  or  inert  gases  should  be  safely  purged 
from  the  downstream  piping  before  any 
attempt is made to light an appliance.  

Appliances should then be started as per the relevant 
appliance manufactures procedures. 

SPECIAL NOTE FOR BOTTLED OR TANK LPG 
GAS SYSTEMS 

Bottled  or  tank  gas  cylinders  contain  pressures  of 
several  thousand  kPa  and  the  Model  750  can  be 
supplied  as  a  high  pressure  version  up  to  150  kPa. 
This  disparity  means  that  the  bottled  or  tank  gas 
system  (which  includes  regulators,  relief  valves  and 
over  pressure  devices)  must  ensure  that  the 
maximum  operating  pressure  of  the  meter  is  not 
exceeded.  

When  tank  filling  or  connecting  fully  pressurised 
bottled  gas  cylinders  into  an  empty  or  near  empty 
system 

EXTREME  CARE

  must  be  taken  not  to 

overload  the  regulator  diaphragms  with  a  sudden 
surge  of  inlet  pressure  (of  several  hundred  to 
thousands kPa). 

So  called  “Change-Over”  regulators  used  in  the 
changing  of  cylinders  are  particularly  susceptible  to 
this problem, when the gas pressure is low. 

This  can  result  in  an  increase  in  outlet  pressure 
greater  than  that  of  the  maximum  operating  pressure 
of  the  meter  and  create  high  differential  pressures 
across  the  meter.  This  can  result  in  damage  to  the 
meters diaphragms and/or internal mechanism. 

To avoid high differential pressures across the 
meter  and/or  pressures  exceeding  the 
maximum  operating  pressure  of  the  meter, 

pressurise the system 

VERY

 

SLOWLY

 to prevent any 

pressure surges into the system. 

INSPECTION & MAINTENANCE 

6. 

Inspection Frequency 

A  properly  installed  and  commissioned  meter  should 
provide many years of trouble free operation, however 

Содержание 750

Страница 1: ... other database of these documents requires the written approval of Landis Gyr Due to continuous product development these details are subject to change without notice Model 750 Gas Meter Installation Commissioning and Maintenance Manual Revision 750002 Model 750 Installation Commissioning and Maintenance Manual 17th May 2016 Landis Gyr ...

Страница 2: ...______________________________________________________________8 STORAGE ________________________________________________________________________________8 TRANSPORTATION ________________________________________________________________________8 INSTALLATION ____________________________________________________________________________8 PUTTING INTO OPERATION ___________________________________________...

Страница 3: ...s that demonstrate the long life and high accuracy for in excess of 20 million cycles Exceeds the endurance testing requirements of both the European Standard EN1359 1999 and the Australian Gas Association AG702 which are in excess of the endurance testing requirements as specified in OMIL Recommendation 31 Pressure Absorption The slow revving operation 2 litres cycle the low friction valve assemb...

Страница 4: ...IMENSIONS MATERIAL OF CONSTRUCTION For more details refer to Document Number 750004 Model 750 Material Weight and Recyclability Table 1 Materials of Construction Material Housing Diecast Aluminium Centre Block PBT polybuylene terephthalate Grid Valves PF Phenoplastic Diaphragm Plates Pans Steel Rods Shafts Steel Valve Guide Steel Diaphragms Moulded PET and Elastomer Index window PC UV Stabilised P...

Страница 5: ...ation to pass initial testing however sustained accuracy over time comes down to the quality the design and construction of the meter Landis Gyr has always recognised that the cost of changing meters in the field coupled with repair costs is significant and a meter with a shorter field life also attracts other costs including uncertain revenue collection and hidden but real cost associated with a ...

Страница 6: ...ge Although magnahelic and transducers can be used to determine absorption and oscillation these devices must be calibrated to the reference standard a the British Slope Gauge as described in AG702 The acceptance criteria for pressure absorption is no greater than 125Pa through all flow rates and for oscillation 75Pa through all flow rates METER ACCURACY TREND Trend is the accuracy at 100 Qmax min...

Страница 7: ...mpleteness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability INDEPENDENT ENDURANCE TESTING RESULTS 0 2 Qmax EN1359 1998 Endurance Test Results Conducted by Independent Accredited Laboratory DVGW Forschungstelle 3 2 1 0 1 2 3 0 5000 10000 15000 20000 25000 30000 Volume m3 5000h Qmax Percentage Error 13627419 ...

Страница 8: ...paired resulting in improper measurement and loss of revenue STORAGE Diaphragm meters should be stored upright in a clean dry place and fitted with dust caps on the inlet and outlet connections This will exclude debris that can be detrimental to the meter s internal components TRANSPORTATION Diaphragm meters should be transported upright be suitably restrained and properly cushioned to prevent the...

Страница 9: ...eam of the meter to be sure that all connections are made up and tight or that the downstream valve if there is one is closed CARE must be taken to prevent excessive flows and high pressure drops across the meter If CARE is not exercised when pressurising the meter over speeding of the meters internal mechanism may result in internal damage to the meter To prevent over speeding the pressure drop a...

Страница 10: ...phide and water Therefore the service life will be dramatically affected accordingly WARNING PURE OXYGEN All regulators and meters supplied by Landis Gyr are NOT SUITABLE for pressure regulating or measuring PURE OXYGEN Special meters and regulators made from specific materials are required to prevent heat build up as a result of friction etc SERVICE LIFE INTERNAL CORROSION Service life varies acc...

Страница 11: ...ning and closing of the reed switch All meters are fitted with a magnet in the last index wheel and hence each meter is pulse retro fittable while in service by use an External Pulse Module without the need to interfere with the metrology of the meter or the meter seals The pulse output is 1 pulse per 10 litres No other pulse output values are available Picture right shows the Model 750 Meter with...

Страница 12: ... 750085 PULSE OUTPUT INSTALLATION INSTRUCTIONS IN Z41 Assembly 1 Push connect pulse cable into Pulse Module Housing 1 IN Z41 Security Sealing Pin Wire 1 Insert sealing Pin 6 into Pulse Module Housing 1 2 Seal using wire length 9 and Lead Seal 10 if desired IN Z41 Installation to Index 1 Attach the pulse module to the meter index 2 Insert Copper Ring 3 and Lead Pin 2 3 Squash Lead Pin 2 using plier...

Страница 13: ...ed Plastic Seal Z4 Z5 3 Reqd 32446710 750013 X Red Plastic Seal NSW EL 3 Reqd 750014 X Red Plastic Seal 750 NZ 3 Reqd 750101 Change Gear for gas meter 3747000 750102 Change Gear for index 3747500 750020 Index Front Facing Complete 750021 Index Screw ISO 7045 M4x8 4 8 H Zn galv 4 Reqd 750022 Index Cover hydrophilic coated 7502XX X Index Plate Printed Customer Specific 750023 index plate source part...

Страница 14: ... o ring 34x2 5 NBR 70 Shore A 3110496 750070 X Meter Assembled w o Index or Badge c w Non Return 750065 Outlet Pipe Complete c w Non Return Valve 750064 Non Return Assembly 750061 Outlet Pipe Moulded 32319623 750062 Top o ring 27x2 NBR 70 Shore A 3110001 750063 Bottom o ring 34x2 5 NBR 70 Shore A 3110496 750031 O ring Top Bottom 3 5x190 NBR 70 Shore A 750066 Replaced by 750031 was 4x190mm 610019 M...

Страница 15: ...lation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability Miscellaneous L0331 Grease Kluber Isoflex Topas NB5051 L0332 Oil Kluber Constant OY32 A0339 Pressure Test Nipple Sealant Accessories BKNut M5 Nyloc Nut 15006 M5x12 Screw Molybond Coated 750080 Box for Four 4 Meters 75008...

Страница 16: ...ng the information in this document Landis Gyr makes no representations in respect of gives no guarantees or undertakings in relation to and to the maximum extent permitted by law excludes all warranties in relation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability ASSEMBLY DR...

Страница 17: ...able care in reviewing the information in this document Landis Gyr makes no representations in respect of gives no guarantees or undertakings in relation to and to the maximum extent permitted by law excludes all warranties in relation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and rel...

Отзывы: