inspections  should  be  conducted  as  and  when 
required. 

Additional  inspections  maybe  necessary  for  example 
natural  disasters,  earthquakes,  floods,  landslides, 
house fires etc. 

When  the  meter  is  used  in  adverse  environments  or 
with  gases  high  in  contaminants  more  frequent 
inspections should be conducted. 

 

SUITABLE GASES 

Model  750  Gas  Meter  and  300  Series  Domestic 
Regulators  are  suitable  for  use  with  a  variety  gases 
such as: 

  Natural Gas, 

  Methane, 

  Liquefied Petroleum Gas (LPG), 

  Town Gas (TG), 

  Butane, 

  Propane, 

  Nitrogen, 

  Carbon Dioxide (dry), 

  Carbon Monoxide (dry), 

  Aliphatic Hydrocarbons, 

  Air 

  and inert gases 

For gases not listed please consult  Gyr. 

BIO-GAS 

Biogas  is  generated  when  bacteria  degrades 
biological  material  in  the  absence  of  oxygen,  in  a 
process  known  as  anaerobic  digestion.  Biogas  is 
produced  from marshes,  rubbish  dumps,  septic  tanks 
and  waste  treatment  plants.  Biogas  consists  of  large 
quantities  of  carbon  dioxide,  hydrogen  sulphide  and 
water.  Therefore  the  service  life  will  be  dramatically 
affected accordingly. 

 

WARNING! PURE OXYGEN 

All  regulators  and  meters  supplied  by  Landis  +  Gyr 
are 

NOT  SUITABLE

  for  pressure  regulating  or 

measuring 

PURE  OXYGEN

.  Special  meters  and 

regulators  made  from  specific  materials  are  required 
to prevent heat build up as a result of friction etc. 

 

SERVICE LIFE 

– INTERNAL CORROSION 

Service  life  varies  according  to  deleterious  effects  of 
the  specific  gas,  the  level  of  filtration  and  any 
contaminants  in  the  gas  stream.  For  example  gases 
containing  water,  sulphur,  nitrous  oxides  and  carbon 
dioxide  can  accelerate  corrosion  to  an  unacceptable 
level.  Seemingly  innocuous  gases,  under  certain 

conditions,  are  surprisingly  corrosive  capable  of 
producing  such  compounds  as  carbonic  acid, 
sulphurous  acid  and  sulphuric  acid.  Nitrous  oxides 
(NOx) attack rubber and plastic components. 

 

METER BAR OPTIONS 

An  optional  meter  bar  is  available  for  wall  or  pole 
mounting of a meter and / or regulator off the ground. 
The  meter  bar  comes  with  two  models  503700 
(without plug cap) and 503800 (with plug cap) 

 

Meter Bar (503800)

 

Table 5 : Domestic Meter Bar Options

 

Part Number 503700 
3 x Cap Nuts ( p/n 138 ) 
3 x ¾” Liners ( p/n 503606 ) 
3 x 26e Washers ( p/n 26 ) 
1 x ¾” BSP Female to 10 Lt. Male Adaptor (p/n 503-6) 
Part Number 503800 
3 x Cap Nuts ( p/n 138 ) 
3 x ¾” Liners ( p/n 503606 ) 
3 x 26e Washers ( p/n 26 ) 
1 x ¾” BSP Female to 10 Lt. Male Adaptor (p/n 503-6) 
1 x Plug Cap( p/n 000209 ) 

 

METER CONNECTION OPTIONS 

The  meter  boss  threads  are  vertical  inlet/outlet  10 
Light 1” to BS746 1987 at 152.4mm ( 6” ) centres. 

There are a variety of meter connection kits available. 
The  standard  kit  is  a 

1”  10  Lt.  Cap  Nut  to  ¾”  BSP 

Liner set as detailed below. 

Table 6 : SK5 Connection Kit

 

Part Number SK5 
2 x Cap Nuts ( p/n 138 ) 
2 x ¾” BSP Liners ( p/n 144-1 ) 
2 x 26e Washers ( p/n 26 ) 

 

 

 

Содержание 750

Страница 1: ... other database of these documents requires the written approval of Landis Gyr Due to continuous product development these details are subject to change without notice Model 750 Gas Meter Installation Commissioning and Maintenance Manual Revision 750002 Model 750 Installation Commissioning and Maintenance Manual 17th May 2016 Landis Gyr ...

Страница 2: ...______________________________________________________________8 STORAGE ________________________________________________________________________________8 TRANSPORTATION ________________________________________________________________________8 INSTALLATION ____________________________________________________________________________8 PUTTING INTO OPERATION ___________________________________________...

Страница 3: ...s that demonstrate the long life and high accuracy for in excess of 20 million cycles Exceeds the endurance testing requirements of both the European Standard EN1359 1999 and the Australian Gas Association AG702 which are in excess of the endurance testing requirements as specified in OMIL Recommendation 31 Pressure Absorption The slow revving operation 2 litres cycle the low friction valve assemb...

Страница 4: ...IMENSIONS MATERIAL OF CONSTRUCTION For more details refer to Document Number 750004 Model 750 Material Weight and Recyclability Table 1 Materials of Construction Material Housing Diecast Aluminium Centre Block PBT polybuylene terephthalate Grid Valves PF Phenoplastic Diaphragm Plates Pans Steel Rods Shafts Steel Valve Guide Steel Diaphragms Moulded PET and Elastomer Index window PC UV Stabilised P...

Страница 5: ...ation to pass initial testing however sustained accuracy over time comes down to the quality the design and construction of the meter Landis Gyr has always recognised that the cost of changing meters in the field coupled with repair costs is significant and a meter with a shorter field life also attracts other costs including uncertain revenue collection and hidden but real cost associated with a ...

Страница 6: ...ge Although magnahelic and transducers can be used to determine absorption and oscillation these devices must be calibrated to the reference standard a the British Slope Gauge as described in AG702 The acceptance criteria for pressure absorption is no greater than 125Pa through all flow rates and for oscillation 75Pa through all flow rates METER ACCURACY TREND Trend is the accuracy at 100 Qmax min...

Страница 7: ...mpleteness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability INDEPENDENT ENDURANCE TESTING RESULTS 0 2 Qmax EN1359 1998 Endurance Test Results Conducted by Independent Accredited Laboratory DVGW Forschungstelle 3 2 1 0 1 2 3 0 5000 10000 15000 20000 25000 30000 Volume m3 5000h Qmax Percentage Error 13627419 ...

Страница 8: ...paired resulting in improper measurement and loss of revenue STORAGE Diaphragm meters should be stored upright in a clean dry place and fitted with dust caps on the inlet and outlet connections This will exclude debris that can be detrimental to the meter s internal components TRANSPORTATION Diaphragm meters should be transported upright be suitably restrained and properly cushioned to prevent the...

Страница 9: ...eam of the meter to be sure that all connections are made up and tight or that the downstream valve if there is one is closed CARE must be taken to prevent excessive flows and high pressure drops across the meter If CARE is not exercised when pressurising the meter over speeding of the meters internal mechanism may result in internal damage to the meter To prevent over speeding the pressure drop a...

Страница 10: ...phide and water Therefore the service life will be dramatically affected accordingly WARNING PURE OXYGEN All regulators and meters supplied by Landis Gyr are NOT SUITABLE for pressure regulating or measuring PURE OXYGEN Special meters and regulators made from specific materials are required to prevent heat build up as a result of friction etc SERVICE LIFE INTERNAL CORROSION Service life varies acc...

Страница 11: ...ning and closing of the reed switch All meters are fitted with a magnet in the last index wheel and hence each meter is pulse retro fittable while in service by use an External Pulse Module without the need to interfere with the metrology of the meter or the meter seals The pulse output is 1 pulse per 10 litres No other pulse output values are available Picture right shows the Model 750 Meter with...

Страница 12: ... 750085 PULSE OUTPUT INSTALLATION INSTRUCTIONS IN Z41 Assembly 1 Push connect pulse cable into Pulse Module Housing 1 IN Z41 Security Sealing Pin Wire 1 Insert sealing Pin 6 into Pulse Module Housing 1 2 Seal using wire length 9 and Lead Seal 10 if desired IN Z41 Installation to Index 1 Attach the pulse module to the meter index 2 Insert Copper Ring 3 and Lead Pin 2 3 Squash Lead Pin 2 using plier...

Страница 13: ...ed Plastic Seal Z4 Z5 3 Reqd 32446710 750013 X Red Plastic Seal NSW EL 3 Reqd 750014 X Red Plastic Seal 750 NZ 3 Reqd 750101 Change Gear for gas meter 3747000 750102 Change Gear for index 3747500 750020 Index Front Facing Complete 750021 Index Screw ISO 7045 M4x8 4 8 H Zn galv 4 Reqd 750022 Index Cover hydrophilic coated 7502XX X Index Plate Printed Customer Specific 750023 index plate source part...

Страница 14: ... o ring 34x2 5 NBR 70 Shore A 3110496 750070 X Meter Assembled w o Index or Badge c w Non Return 750065 Outlet Pipe Complete c w Non Return Valve 750064 Non Return Assembly 750061 Outlet Pipe Moulded 32319623 750062 Top o ring 27x2 NBR 70 Shore A 3110001 750063 Bottom o ring 34x2 5 NBR 70 Shore A 3110496 750031 O ring Top Bottom 3 5x190 NBR 70 Shore A 750066 Replaced by 750031 was 4x190mm 610019 M...

Страница 15: ...lation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability Miscellaneous L0331 Grease Kluber Isoflex Topas NB5051 L0332 Oil Kluber Constant OY32 A0339 Pressure Test Nipple Sealant Accessories BKNut M5 Nyloc Nut 15006 M5x12 Screw Molybond Coated 750080 Box for Four 4 Meters 75008...

Страница 16: ...ng the information in this document Landis Gyr makes no representations in respect of gives no guarantees or undertakings in relation to and to the maximum extent permitted by law excludes all warranties in relation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and reliability ASSEMBLY DR...

Страница 17: ...able care in reviewing the information in this document Landis Gyr makes no representations in respect of gives no guarantees or undertakings in relation to and to the maximum extent permitted by law excludes all warranties in relation to the accuracy or completeness of the information in this document Prospective users of this information should make their own enquiries as to its accuracy and rel...

Отзывы: