S8E V3 Hi-Carb Superchiller 

230V / 50Hz  

 

 

www.lancerbeverage.com 

Page 9 of 27 

Hoshizaki Lancer reserve the right to change specifications without notice. 

Part No: 68000021 

Images are for illustration purposes only as product may vary. 

No 043-3 – 19 December 2019 

 

3.12  Purge System 

Progressively activate each dispensing valve or Bargun connected to the Superchiller systems 

until an uninterrupted flow of soda, water (where applicable), and syrup pours from each 

dispenser. 

 

3.13  Sanitise System 

Prepare sanitising solution:  

Prepare sanitising solution in accordance with the manufacturer’s written recommendations 

and safety guidelines. 

 

Sanitising BIB System 

  Remove all disconnects from BIB containers. 

  Immerse all disconnects in warm water and clean using a nylon bristle brush.  Rinse with 

clean water. 

  Prepare sanitising solution according to manufacturer’s instructions. 

  Attach sanitising fittings to BIB disconnects, if sanitising fittings are not available cut fittings 

from empty BIB bags. 

  Immerse all sanitising fittings with attached BIB disconnects in bucket of sanitising solution.  

Operate all dispensing valves until the sanitising solution flows from the valve.  Allow 

sanitiser to remain in lines for fifteen (15) minutes. 

  Immerse all sanitising fittings with attached BIB disconnects in bucket of clean water.  

Operate all dispensing valves until all sanitiser has been flushed from the system.   

  Remove sanitising fittings from BIB disconnects and re-connect disconnects to appropriate 

BIB's.  Operate dispensing valves until syrup flows freely. 

4.  Scheduled Maintenance 

The following Superchiller routine maintenance should be performed at the intervals listed. 

4.1  Daily 

Cleaning/Sanitising 

The Superchiller supplies soda water to the dispensing valves/barguns. To ensure optimum 

drink quality and system performance at all times please follow cleaning and sanitising 

procedures for the dispensing valves/barguns recommended by the valve/bargun 

manufacturer. 

 

Checking CO2 Supply 

Ensure that the contents gauge on the CO2 Regulator reads higher than 1400kpa on the dial. If 

it does not, then the CO2 cylinder is empty and must be changed using safe working practices. 

 

Warning 

To avoid personal injury and/or property damage, always secure the 

CO

2

 cylinder with a safety chain to prevent it from falling over; and use 

appropriate protective equipment (as defined in Clause 3.3.2 of AS 

5034) to handle cylinders.  

Should the valve become accidentally damaged or broken off, a CO

2

 

cylinder can cause serious personnel injury. 

 

4.2  Quarterly 

The Superchiller should be connected to a filtered water supply. To ensure optimum drink 

quality and system performance, supply water filters should be replaced every 3 months. 

 

4.3  Half Yearly 

  Remove & Clean condenser filters on the Superchiller. When the environment is dirty and 

dusty, the interval between cleaning the filters may need to be reduced. Clean condenser 

with low pressure compressed air. When using compressed air always direct air from the 

fan side through condenser. Remove all dust and foreign particles from refrigeration deck. 

Содержание S8E V3 Series

Страница 1: ...www lancerbeverage com S8E V3 Hi Carb Superchiller 230V 50Hz Installation Operation Service Manual...

Страница 2: ...erbeverage com Page 2 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 Decemb...

Страница 3: ...with water 8 3 9 Electrical Connection 8 3 10 Plumbing the drain and CO2 exhaust 8 3 11 Commissioning 8 3 12 Purge System 9 3 13 Sanitise System 9 4 Scheduled Maintenance 9 4 1 Daily 9 4 2 Quarterly 9...

Страница 4: ...80 litres Construction Stainless Steel Compressor Danfoss x 2 Agitator Motor 12W 230 VAC 1 Phase Condenser Motor 20W 230 VAC 1 Phase Ice bank Control Electronic Carbonation Level Control Electronic Dr...

Страница 5: ...n injury or equipment damage 2 3 Operating Warning Superchillers are intended for indoor operation only do not operate outside unless suitably protected by a weatherproof enclosure This appliance is n...

Страница 6: ...m with the carrier 3 2 Unpacking Caution The use of gloves is recommended to protect hands from potential injury from sharp edges The Superchiller must always be handled in a vertical position Careful...

Страница 7: ...carbonator or 3 pumps single carbonator python should be connected to Chiller as follows 5 Pump 4 Pump 3 Pump SODA RETURN A WATER RETURN SODA RETURN B SODA RETURN A SODA RETURN B SODA RETURN A WATER R...

Страница 8: ...requires a separate 10 amp Postmix and a 15amp Refrigeration power supplies Check the name plate on the machine for electrical supply requirements Use only the power supply specified on the name plate...

Страница 9: ...nnects and re connect disconnects to appropriate BIB s Operate dispensing valves until syrup flows freely 4 Scheduled Maintenance The following Superchiller routine maintenance should be performed at...

Страница 10: ...res per minute replace pump Commission and purge system as per clause 6 11 and 6 12 4 5 Sanitisation of Beverage System To maintain optimum quality of dispensed product each Superchiller and its assoc...

Страница 11: ...age 11 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 December 2019 5 Postm...

Страница 12: ...of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 December 2019 5 2 Twin Carb...

Страница 13: ...13 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 December 2019 5 4 Twin Ca...

Страница 14: ...om Page 14 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 December 2019 6 E...

Страница 15: ...lancerbeverage com Page 15 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19...

Страница 16: ...z www lancerbeverage com Page 16 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043...

Страница 17: ...if necessary fit burnout drier to industry standards Compressor short cycling on thermal overload frequent starting and stopping of the compressor while ice bank control contacts remain closed Dirty...

Страница 18: ...aper cups Dirty or greasy glasses Improperly drawn drink Check carbonator control using procedure on page 21 Replace control or probe if defective Check filters Check CO2 pressure at regulator Should...

Страница 19: ...ll not run due to excessive carbonator CO2 pressure Faulty low pressure switch Defective Carbonator motor Locked up pump Motor has cut out on overload Carbonator empty faulty control board or level pr...

Страница 20: ...VAC is present on terminals N A ON 1 ON 2 terminals Work should only be performed by fully trained certified Electrical Plumbing Refrigeration Technicians 1 Remove the ice bank probe connections from...

Страница 21: ...ning 230VAC is present on terminals N A ON 1 ON 2 Work should only be performed by fully trained certified Electrical Plumbing Refrigeration Technicians 1 Remove the carbonator probe connections from...

Страница 22: ...9 BACKFLOW PREV ANDERSON 6 08000002 CARBONATOR RELIEF VALVE 7 63000163 COIL ASSY PRECHILL B 8 87000052 STRAINER FLOW INDICATOR 10 63000164 COIL ASSY SODA A 11 63000165 COIL ASSY SODA B 12 63000205 COI...

Страница 23: ...lancerbeverage com Page 23 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 D...

Страница 24: ...8 83000324 ELECTRICAL BOX ASSY 4P 5P S8E V2 83000325 ELECTRICAL BOX ASSY 3P S8E V2 9 83600811 MINI CONTACTOR C15 9 DANFOSS 10 83000278 CONTROL LEVEL I B HYDRA R2 11 83000282 COMPRESSOR START RELAY AN...

Страница 25: ...cerbeverage com Page 25 of 27 Hoshizaki Lancer reserve the right to change specifications without notice Part No 68000021 Images are for illustration purposes only as product may vary No 043 3 19 Dece...

Страница 26: ...of the Divisional Sales Manager Lancer may choose to reimburse the customer for some or all labour costs associated with a warranty claim Any claim for labour costs must be authorized by Lancer prior...

Страница 27: ...nd pumps secured and mounted correctly in correct locations All pumps run quietly and carbonator pump switched ON OFF Check icebank probe position and tightness and correct wiring of harness Carbonato...

Отзывы: