LP2 Superchiller
230V / 50Hz
lancerbeverage.com
Page 10 of 27
Hoshizaki Lancer reserve the right to change specifications without notice.
No 023b – 12 November 2012
Images are for illustration purposes only as product may vary.
Warning
To avoid possible fatal electric shock or serious injury the
Superchiller must be electrically grounded.
Electrical Connection Must Be Made In Accordance With The
Appropriate Local Codes And Regulations.
Use of an RCD is recommended.
6.10
Plumbing the drain and CO2 exhaust
The 13mm overflow drain tube exiting from the front panel of the unit should be plumbed to a suitable
drain, installation in accordance with AS/NZS 3500.1 and AS/NZS 3500.2.
The 6mm barb labelled as CO
2
EXHAUST should be plumbed to an outside safe area.
6.11
Commissioning
Unplug recirculation pump power supply lead from wiring harness located under lid.
Connect Superchiller power supply lead to an appropriate 3 pin socket 10 Amp outlet and
switch on. Compressors, condenser fans and agitator motors should all operate.
When Superchiller ice bank is fully formed (approx. 3 hours) the compressors and condenser
fans will cycle off, but agitator will run continuously (unit has cycled off).
Note:
The agitator will run at high speed initially (approx. 1500rpm) but will change to a slow
speed (approx. 300rpm) 3 minutes after carbonator pump de-energises.
After Superchiller has cycled off, reconnect recirculation pumps.
6.12
Purge System
Progressively activate each dispensing valve or Bargun connected to the Superchiller systems until
an uninterrupted flow of soda, water (where applicable), and syrup pours from each dispenser.