PAGE 9

WATER SOFTENER

PRESSURE

TANK

BYPASS PLUMBING

RECOMMENDED

IF

OPTIONAL BP2000

BYPASS VALVE

IS NOT USED.

BRINE TANK

FROM

WELL PUMP

MINIMUM 10 FEET

BETWEEN

WATER SOFTENER OUTLET

AND

WATER HEATER INLET

WATER SOFTENER

BYPASS PLUMBING

RECOMMENDED

IF

OPTIONAL BP2000

BYPASS VALVE

IS NOT USED.

TO

DRAIN

TO

OUTSIDE

TAP

BRINE TANK

WATER

HEATER

DRAIN LINE

AIR GAP

ADAPTER

FROM

WATER MAIN

COLD

HOT

MINIMUM 10 FEET

BETWEEN

WATER SOFTENER OUTLET

AND

WATER HEATER INLET

LOCATE WATER SOFTENER

AS CLOSE AS POSSIBLE

TO BRINE TANK.

A SIX FOOT LENGTH OF 3/8" O.D.

BRINE LINE POLYTUBE

SUPPLIED WITH BRINE TANK.

OVERFLOW GRAVITY DRAIN - ONLY USED IN CASE OF MALFUNCTION IN THE BRINE SHUTOFF. DO NOT CONNECT TO CONTROL VALVE DRAIN LINE.

IF UNIT IS INSTALLED WHERE OVERFLOW COULD CAUSE WATER DAMAGE, CONNECT TUBING AND RUN TO FLOOR DRAIN. DO NOT RUN TUBING ABOVE OVERFLOW HEIGHT.

WELL WATER

INSTALLATION

CITY WATER

INSTALLATION

WATER

METER

TO

DRAIN

TO

OUTSIDE

TAP

WATER

HEATER

DRAIN LINE

AIR GAP

ADAPTER

COLD

HOT

LOCATE WATER SOFTENER

AS CLOSE AS POSSIBLE

TO BRINE TANK.

A SIX FOOT LENGTH OF 3/8" O.D.

BRINE LINE POLYTUBE

SUPPLIED WITH BRINE TANK.

LOCATE WATER SOFTENER CLOSE TO A DRAIN.

AVOID OVERHEAD DRAIN LINES IF POSSIBLE TO

PREVENT BACK PRESSURE ON BRINE INJECTOR.

IF OVERHEAD DRAIN LINE IS USED AND EXCEEDS

5 FEET ABOVE CONNECTION ON CONTROL VALVE

OR

IF DRAIN LINE EXCEEDS 20 FEET IN LENGTH,

DRAIN LINE PIPE SIZE SHOULD BE MINIMUM 3/4".

OVERFLOW GRAVITY DRAIN - ONLY USED IN CASE OF MALFUNCTION IN THE BRINE SHUTOFF. DO NOT CONNECT TO CONTROL VALVE DRAIN LINE.

IF UNIT IS INSTALLED WHERE OVERFLOW COULD CAUSE WATER DAMAGE, CONNECT TUBING AND RUN TO FLOOR DRAIN. DO NOT RUN TUBING ABOVE OVERFLOW HEIGHT.

LOCATE WATER SOFTENER CLOSE TO A DRAIN.

AVOID OVERHEAD DRAIN LINES IF POSSIBLE TO

PREVENT BACK PRESSURE ON BRINE INJECTOR.

IF OVERHEAD DRAIN LINE IS USED AND EXCEEDS

5 FEET ABOVE CONNECTION ON CONTROL VALVE

OR

IF DRAIN LINE EXCEEDS 20 FEET IN LENGTH,

DRAIN LINE PIPE SIZE SHOULD BE MINIMUM 3/4".

Click to buy NOW!

PD

F-XCHANGE

w

ww

.docu-track.c

om

Click to buy NOW!

PD

F-XCHANGE

w

ww

.docu-track.c

om

Do not add salt to the brine tank yet. Do not plug the transformer into the receptacle yet. Make sure inlet and outlet valves are to their 

closed positions. If using optional bypass, place in bypass position. Turn on main water supply. Open a cold water faucet. This will clear 

the line of any debris (solder, pipe dope, etc.) that may be in the line. Let water run at faucet for a couple minutes, or until clear. Turn 

off faucet. Manually add 1 ½  gallons of water to the brine tank. Now plug the transformer into a 120 volt receptacle (be certain the 

receptacle is uninterrupted). Within 5 seconds the control display and buttons will illuminate and the time of day screen will appear.

• 

 Press and hold the 

REGEN

 button for approximately 5 seconds until the motor starts.

• 

 Wait until display reads 

FILL

 and numbers start counting down.

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

SOFTENING

 position.

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

BACKWASH 

position. (NA for model 7-LXC-50, -100)

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

REGENERANT DRAW

 position.

• 

 Momentarily press 

REGEN

 again. Valve is  now in the second 

BACKWASH 

position. (NA for model 7-LXC-50, -100)

If using optional bypass 

SLOWLY

 turn bypass valve to 

DIAGNOSTIC

 position (

See figure 3 on page 5

) or slowly open inlet valve to 

allow water to slowly enter Softener.

When water is flowing steadily to drain without the presence of air, momentarily press 

REGEN

 

again. Display will read 

RINSE

. Open 

the outlet valve of the softener, or if using optional bypass place to 

NORMAL OPERATION  MODE

 (

see figure 1 on page  

5

). Allow control to finish the 

RINSE 

cycle. Allow the control to automatically advance to the 

SOFTENING

 position. Now 

load the brine tank with salt. Solar Salt is recommended. The brine tank salt level should be checked every couple of 

weeks to determine salt usage. Keeping the brine tank salt level at least 1/2 full is recommended.

SANITIZING:

 Use 2 oz. of 5 ¼% unscented household chlorine bleach for each cubic foot of resin. Pour bleach directly into the 4” 

diameter white brine well located inside the brine tank. Press and hold the 

REGEN

 for 5 - 6 seconds until the motor starts running. Allow 

system to complete the regeneration automatically. Check for other local and state codes which may also specify sanitation methods.

Note: The first step of the regeneration process is to fill the brine tank with the proper amount of water. The brine tank will 

only have a very slight amount of water in it after the regeneration cycles are completed.

PLACING SOFTENER INTO SERVICE

GENERAL OPERATION

User Displays

When the system is in normal service mode, one of up to five 

available User Displays will be shown. Pressing 

NEXT

 will 

alternate between the following displays:

 

• Current time of day

 

• Treated water flow rate

 

• Service contact name and phone number (if entered)

 

• Remaining Capacity of treated water available

 

• Remaining days to regeneration (if Day Override is

    

programmed)

Pressing the 

 button while in the Capacity Remaining or 

Days Remaining displays will decrease the capacity remaining 

in ten gallon increments or the days remaining in one day 

increments. 

To clear the Service Call reminder

, press the 

 and 

  

buttons simultaneously while the number and banner text 

screen is displayed.

If the system has called for a regeneration that will occur at 

the preset time of regeneration, the words REGEN TODAY will 

alternate with the header on the display. 

Utilizing the control valve’s built-in water meter, a water drop 

flashes on the display when water is being treated (i.e. water is 

flowing through the system).

Drop will flash while water 

is being treated.

NEXT

NEXT

NEXT

Contact Screen

NEXT

Note: As an energy saving feature, the control will automatically turn off all SOLID BLUE or SOLID GREEN display 

illumination and keypad illumination after about 5 minutes of the last keypad button push. Any further keypad touch will 

cause the re-illumination of the display and keypad, and re-activate keypad control.

Содержание diamond 7-LXC-50B

Страница 1: ...free service When installed in accordance with the following instructions and if given reasonable care clear soft water will be the result For servicing and future inspection purposes please file this...

Страница 2: ...ss Note Add 4 grains per gallon of hardness for each ppm iron for total compensated hardness Total Grains per Day INSTALLATION DATE SERIAL NUMBER INSTALLER NAME PHONE ADDRESS TABLE OF CONTENTS Job Spe...

Страница 3: ...nt cement on any part of the o rings split rings bypass valve or control valve Plug into an electrical outlet Note All electrical connections must be connected according to local codes Be certain the...

Страница 4: ...the softener cannot be subject to a vacuum due to loss of pressure such as a water main break or submersible well pump check valve failure WATER TEMPERATURE The range of water temperature is 40 F to 1...

Страница 5: ...ility without the need for tools The bypass body and rotors are glass filled Noryl or equivalent and the nuts and caps are glass filled polypropylene All seals are self lubricating EPDM to help preven...

Страница 6: ...ical plumbing should be done in accordance to all local codes INSTALLATION INSTRUCTIONS BRINE LINE FITTING CONNECTIONS DRAIN LINE FITTING CONNECTION USING 5 8 POLY TUBE C l i c k t o b u y N O W PDF X...

Страница 7: ...the control valve with a locking clip The locking clip allows the elbow to rotate 270 degrees so the outlet can be oriented towards the brine tank 8 Connect the brine line polytubing found with the b...

Страница 8: ...HEATER DRAIN LINE AIR GAP ADAPTER COLD HOT LOCATE WATER SOFTENER AS CLOSE AS POSSIBLE TO BRINE TANK A SIX FOOT LENGTH OF 3 8 O D BRINE LINE POLYTUBE SUPPLIED WITH BRINE TANK LOCATE WATER SOFTENER CLO...

Страница 9: ...full is recommended SANITIZING Use 2 oz of 5 unscented household chlorine bleach for each cubic foot of resin Pour bleach directly into the 4 diameter white brine well located inside the brine tank P...

Страница 10: ...Set the amount of hardness in grains of hardness as calcium carbonate per gallon using the or buttons The default is 20 with value ranges from 1 to 150 in 1 grain increments Note The grains per gallon...

Страница 11: ...urn to previous digit Banner Text Set the banner text up to a maximum of 44 characters Use the or to select letters of the alphabet numbers ampersand or a space in the banner text Press NEXT to forwar...

Страница 12: ...Adaptor Input Voltage Hertz 120V AC 60 Hz AC Adaptor Output Voltage Current 12V AC 500 mA 3 Volt Lithium Coin Cell Battery type 2032 PC Board Relay Terminal Block DC Output Voltage 12V DC Relay Speci...

Страница 13: ...7 2 7 4 2 Brine Line Re Fill Flow Control GPM 0 5 0 5 0 5 0 5 0 5 Injector color 1C Violet 1E White 1E White 1F Blue 1H Green X FACTOR SERIES LXC SPECIFICATIONS MODEL NUMBER 7 LXC 50B PACKED BED 7 LX...

Страница 14: ...3 0 4 5 6 0 9 0 Medium 4 0 5 3 8 0 10 7 16 0 High 7 5 10 0 15 0 20 0 30 0 GALLONS WATER TO DRAIN at 40 50 60 PSI Inlet Pressure Low 38 4 39 6 40 4 60 8 62 5 63 8 61 5 63 3 64 5 94 5 96 3 98 0 142 5 14...

Страница 15: ...0 Re FILL Minutes Low 1 5 2 3 3 0 Medium 2 7 4 0 5 3 High 5 0 7 5 10 0 GALLONS WATER TO DRAIN at 40 50 60 PSI Inlet Pressure Low 18 5 20 0 21 3 60 4 62 1 63 4 26 8 28 5 29 8 Medium 19 0 20 6 21 8 61...

Страница 16: ...39 LBS Ion Exchange Resin for Model 7 LX 75B 1 A4074 1 Cu Ft 52 LBS Ion Exchange Resin for Model 7 LX 100B 1 A4074 1 1 2 Cu Ft 78 LBS Ion Exchange Resin for Model 7 LX 150B 1 A4074 2 Cu Ft 104 LBS Ion...

Страница 17: ...ging the power adapter from the wall Battery Fully Seated When replacing the battery align positives and push down to fully seat X FACTOR FRONT COVER AND DRIVE ASSEMBLY After completing any valve main...

Страница 18: ...on caps and or tap with a hammer 1 2 3 4 5 INJECTOR CAP INJECTOR SCREEN INJECTOR PLUG AND O RING Drawing No Order No Description Qty 1 V3005 Spacer Stack Assembly 1 2 V3004 Drive Cap Assy 1 3 V3178LP...

Страница 19: ...ith the service spanner wrench If necessary a pliers can be used to unscrew the nut or cap Do not use a pipe wrench to tighten or loosen nuts or caps Do not place a screwdriver in slots on caps and or...

Страница 20: ...r Assembly Drawing No Order No Description Quantity 1 V3151 Nut 1 Quick Connect 2 2 V3150 Split Ring 2 3 V3105 O Ring 215 2 4 V3191 Vertical Adapter 2 INSTALLATION FITTING ASSEMBLIES 4 Water Flow Prop...

Страница 21: ...V3148 Bypass Rotor Seal Retainer 2 8 V3152 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 BYPASS VALVE Order No V3193 Although no tools are necessary to assemble or disassemble the valve the...

Страница 22: ...der No V3007 07 Description Fitting 1 1 PVC Solvent Assembly Drawing No Order No Description Quantity 1 V3151 Nut 1 Quick Connect 2 2 V3150 Split Ring 2 3 V3105 O Ring 215 2 4 V3352 Fitting 1 1 PVC So...

Страница 23: ...abinetAsm_1 15 XX 1 64 MODEL 005 DWG X CabinetAsm_GeneralDim18 X XX X 0 5 Units Inch ORDERING INFORMATION The cabinet requires two part numbers when ordering one part number for the base assembly w sy...

Страница 24: ...esistance is felt before latching then notches are not fully engaged the piston rod is not in hole the wires are jammed between the drive bracket and drive back plate or the gear is not engaging the d...

Страница 25: ...n the drive cap assembly Continue to tighten the drive cap assembly using a screwdriver as a ratchet until the black o ring on the spacer stack assembly is no longer visible through the drain port Exc...

Страница 26: ...not be used to clean the injector Scoring the injector or increasing the diameter of the hole could change the operating parameters of the injector Push the plug s and or injectors firmly in place re...

Страница 27: ...ace meter f Defective PC Board f Replace PC Board 4 Control valve regenerates at wrong time of day a Power outage a Reset time of day If PC Board has battery back up present the battery may be deplete...

Страница 28: ...leaking fixtures that may be exhausting capacity or system is undersized 10 Residual regenerant being delivered to service a Low water pressure a Check incoming water pressure water pressure must rem...

Страница 29: ...supply from PC Board for 5 seconds and then reconnect c Missing reduction gears c Replace missing gears 15 Err 102 Control valve motor ran too short and was unable to find the next cycle position and...

Страница 30: ...or disconnect power supply from PC Board for 5 seconds and then reconnect Then re program valve to proper setting b MAV NHBP motor wire not connected to PC Board b Connect MAV NHBP motor to PC Board t...

Отзывы: