40
Call 1-888-370-6531 for Technical Support
12.
Trim rubber boot to correct size according to markings on boot and double-
wall pipe size. NOTE: 6-inch double-wall pipe has an outer diameter of 8
inches.
13.
Slide boot over pipe and down onto roof.
14.
Liberally apply sealant under base perimeter of boot. Form boot to roof
surface and screw metal-lined edge to roof using remaining self-drilling
screws evenly spaced (or appropriate fasteners for roof material.)
15.
Apply sealant all the way around the top of boot.
16.
NOTE: Top of piping must be at least 3 feet higher than roof where exited and at least 2 feet higher than any
portion of roof within 10 feet. Additional pipe sections may be purchased to extend the pipe higher if required.
If going over 5 feet above roof, as extended roof support should be added (part # 4913).
17.
Install rain cap to top of pipe. Twist to lock in place.
INSIDE
18.
Relocate or uncover heater. Install tee and draft control, crimped side down, into exhaust outlet on top.
19.
Install crimped to black pipe adapter into tee.
20.
Install single-wall black pipe up to near the end of the double-wall pipe. NOTE: Single-wall pipe must have a
minimum clearance of 18 inches from any combustible materials. Also, single-wall flue piping should never be
used on the exterior of building.
21.
Install slip connector into last piece of black pipe.
22.
Slide firestop plate over double-wall pipe and against roof. Secure in place with sheet metal screws into double
wall pipe.
23.
Install finishing collar into end of double-wall pipe, twist to lock in place.
24.
Slide slip connector up and secure to the finishing collar with three sheet metal screws.
25.
Ensure piping is vertically level and secure tee, adapter and black piping at each joint with at least three sheet
metal screws.
Rubber
Содержание MX 75
Страница 2: ......
Страница 41: ...8 Appendices 8 1 Wiring Diagram ...
Страница 42: ......
Страница 43: ...34 Call 1 888 370 6531 for Technical Support 8 2 Primary Control Instructions ...
Страница 44: ...35 Call 1 888 370 6531 for Technical Support Not used with RES 75 kBTU h units ...
Страница 45: ...36 Call 1 888 370 6531 for Technical Support No latch up with RES 75 kBTU h units ...
Страница 46: ...37 Call 1 888 370 6531 for Technical Support ...
Страница 54: ...45 Call 1 888 370 6531 for Technical Support 9 ...