61
8
Correcting Faults
8
Correcting Faults
8.1
Faults and Warnings
Faults are indicated by the red flashing of the ENTER key and shown in the display. After the
ENTER key is pressed, faults can be reset.
NOTICE
In the case of faults that cannot be allocated, data records can be read with LSB remote soft-
ware and sent to LAMTEC for analysis!
NOTICE
Each fault can occur as a temporary or permanent fault. Temporary faults reset themselves
automatically when the corresponding values lie within the permissible range again.
If temporary faults are present for longer than 30 minutes or repeat several times within an
hour, they become permanent faults. A permanent fault remains even after switching voltage
off and on again. Permanent faults must be reset manually. After a fault reset, the device re-
sets and starts again in COLD START mode.
F
W
H
U
001
/1
Fault
Warning
Main processor
Monitoring processor
Fault number
Probe/probe voltage fault
Trigger 1
Fault 001
Fault 002 - 008
Fault 015 - 016
Number of triggers,
temporary
10 x for at least 10 s 3 x for at least 10 s
Immediately
Time window
60 min
60 min
60 min
Permanent time
30 min
30 min
30 min
Содержание LT3-F
Страница 2: ......
Страница 14: ...13 3 Product Description 3 2 Declaration of Conformity...
Страница 15: ...14 3 Product Description...
Страница 20: ...19 5 Display and Operational Controls 5 2 2 Information Menu Structure 5 2 3 Calibration Menu Structure...
Страница 21: ...20 5 Display and Operational Controls 5 2 4 Settings Menu Structure...
Страница 24: ...23 5 Display and Operational Controls 5 4 1 Main Menu Password Entry...