Product Description
3.6.4
Common technical data for GFI 48/70/89 pilot burner
NOTICE
The electrical data are identical for all devices, only the air and gas volume flows differ.
Design A: Power supply voltage connection
Electrical data
120/127/220/230 VAC; -15/+10% (within the scope of the EU
Gas Appliances Directive), cf. rating plate
240 VAC; -20/+5% (outside the scope of the EU Gas Appli-
ances Directive), cf. rating plate
Mains frequency
50/60 Hz
Power consumption
10 VA flame scanner when UN = 230 V, 230 VA ignition trans-
former,
10 VA flame scanner when UN = 120 V, 192 VA ignition trans-
former,
Ignition transformer duty cycle
ED= 50% on 2 min. (1’ on; 1’ off)
45 °C when UN=230V
ED= 15% on 1 min. (9”on; 51” off) -20°C<Ta<60°C when
UN=120V
Design A: connection to relays
Electrical data
NO contact
NO contact (flame on)
Switching voltage
1
≤
230 V or
≤
48 VDC
Switching current
1, 2
max. 0.5 A cos
ᵠ
0.4 min 10 mA
Contact fusing (internal, soldered):
0.5 AT
Versions A and B: Integrated flame scanner
Ionisation input
Ionisation current
from 1
μ
ADC flame ON
Operating mode
Continuous operation capable
Flame signal output contact
Contact type
Safety-oriented, floating contact
Contact type
NO, for "flame on", the contact is closed
Level of protection
SKII, base isolation for the status signal
Permissible switching voltage
1
≤
230 VAC
≤
48 VDC
Permissible switching current
1, 2
Max. 0.5 A cos
ᵠ
0.4 Min. 10 mA
Contact fusing
0.5 AT (internal, soldered)
Safety time (FFDT)
Response time in the event of the flame going
out
t
V
off 1 s
Switch-on time
t
V
on
≤
1 s
Measuring shunt
runs mains potential
Transmission ratio of measurement voltage to
ionisation current
10 mV (DC) = 1
μ
A (DC)