2.4
Proper Use - Conditions of Use
Intended use
The ignition burner is utilised in industrial ovens, thermal processing systems and heating boil-
ers for gas, oil and solid fuels.
It is used for the following purposes:
•
Preheating the system
•
Igniting the main burner
•
Supporting the main burner flame
The ignition burner is intended only for the described use.
Any use going beyond the intended use shall be deemed improper.
The LAMTEC GmbH & Co KG shall not be liable for damage caused by the non-compliance.
2.5
Installation Notes
WARNING!
All following warnings must be observed to avoid personal injury and damage to
property and the environment..
Supply the feed cable with L, N and PE only. The neutral conductor may not have any
potential difference to PE.
Phase and neutral conductors may not be interchanged (this would lead to dangerous
malfunctioning, loss of protection against contact, etc.).
The supply cable of the integrated flame scanner must absolutely be fused with a 4 A
(slow) fuse. The minimum fusing amounts to 0.5A..