6 Appendix
6.2
Fault Codes
NOTICE
The LAMTEC burner controls use different methods to detect fault messages between main
processor and watchdog processor:
BT300/ETAMATIC/FMS/VMS/FA1:
The bus transmission does not generally use different fault numbers to distinguish between
watchdog processor and main processor faults. In order to distinguish the main processor fault
messages from the watchdog processor fault messages, an offset of 10000 is added to the
watchdog processor faults. The main processor fault message H002 becomes the watchdog
processor fault message U10002.
CMS:
CMS allocates different fault numbers to main processor and watchdog processor faults.
An offset is not necessary.
Fault
Code
No.
Restart according to
Description
TRD
EN676
001
0
3
Ignition flame does not appear.
002
0
0
parasitic light failure
003
0
3
Flame fault during ignition
004
1
1
Flame fault during operation
005
0
3
Flame signal does not appear during 1st safety time
006
0
3
Flame signal goes out during stabilising time
007
0
3
The flame signal extinguishes during the first safety time
008
0
0
The flame signal extinguishes during the second safety time
009
0
0
Flame signal does not appear during safety time
010
0
0
Flame signal goes out immediately after ignition
141
0
0
Potentiometer faulty, feedback changing too quickly: channel 1
142
0
0
Potentiometer faulty, feedback changing too quickly: channel 2
143
0
0
Potentiometer faulty, feedback changing too quickly: channel 3
144
0
0
Potentiometer faulty, feedback changing too quickly: channel 4
161
>88
3
Monitoring direction of ratation: channel 1
162
>88
3
Monitoring direction of ratation: channel 2
163
>88
3
Monitoring direction of ratation: channel 3
164
>88
3
Monitoring direction of ratation: channel 4
171
>88
3
Dead band over range too long: channel 1
172
>88
3
Dead band over range too long: channel 2
173
>88
3
Dead band over range too long: channel 3
174
>88
3
Dead band over range too long: channel 4
181
>88
3
Dead band under range too long: channel1
182
>88
3
Dead band under range too long: channel 2
183
>88
3
Dead band under range too long: channel 3
184
>88
3
Dead band under range too long: channel 4
191
1
1
1st monitoring band over range too long: channel 1
192
1
1
1st monitoring band over range too long. Channel: 2