4 Operation
The total of running times for curve set 1and curve set 2 do not necessarily add up to the dis
-
played total running time.
NOTICE
The total counter refers to the ETAMATIC V 's running time. It starts timing as soon as the unit
is connected to a voltage source (this also provides the basis for the fault history).
The individual running time counters refer to the burner's running time. They start timing as
soon as the burner is in operation with the relevant curve set (flame signal is present).
4.11
Displaying Checksums and Safety Times
1
st
safety time oil in seconds
2
nd
safety time oil in seconds
1
st
safety time gas in seconds
2
nd
safety time gas in seconds
pre-purge time in seconds
If you have changed parameters, reset the ETAMATIC V. Only a reset refreshes a checksum.
Press keys 16 and 17 to select "setpoint feedback”.
Press key 11 ENTER.
The following values are displayed one by one:
CRC 16 of the levels 0, 1 and 2: adjustable at commissioning time
4: adjustable by LAMTEC only
To exit, press the 1 RESET button