![Lamtec ETAMATIC V Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/lamtec/etamatic-v/etamatic-v_quick-reference_3453925012.webp)
11
4 Operation
4
Operation
4.1
Reading Faults
NOTICE
Press key 16 for reading other display values at time of the fault. All display values are frozen.
4.2
Resetting Faults
4.3
Recalling Fault History
The ETAMATIC V stores the last 10 faults with the associated data of the running time counter.
Requirement: ETAMATIC V must not be in fault condition.
NOTICE
If it is certain that the ETAMATIC V has carried a voltage at all times since the last fault, it is
possible, that from the present output of the running time counter and the current time, to de
-
termine at which time the fault occurred.
Red fault LED is on
Press key 17 to get STATUS → display fault code
Press key ENTER → Plain text message is shown on display (incl. output of running
time counter)
Press key RESET
Alternatively:
Use an external switch to send a short signal (min. 2 sec.) to terminal 57.
The error is cleared!
Press key 17 until the display shows "Status".
Press key 3 → the display shows the last fault code
Press key 11 (Enter) → the display shows the associated plain text and the running
time hours.
Press key 3 again → the display shows the last but one fault code.
Press keys 3 and 2 to browse through the fault history.