background image

13

Ground Source Heat Pumps Since 1983

Possible problems during startup

Problem

Cause

Solution

Fuses always blow when the compressor is 
being started.

You are using the wrong type of fuse.

Check that the fuse is automatic: C or D/
ceramic fuse: SLOW or with a snail icon.

Temporary connections at the site are 
causing an overload on the fuses.

Reduce load.

The ground loop pump does not start.

The regulator may not be getting any 
power.

Check the regulator fuse.

The regulator is not authorised to start the 
pump.

Check the measured/set values.

The ground loop pump does not circulate 
fluid.

The brine pump is rotating in the wrong 
direction.

Switch the location of the two phases.

Shut-off valves are in the fill position.

Check that the deaeration and fill valves 
are in the ‘closed’ position and that the 
intermediate valve is open.

The compressor runs for a little while and 
the steam pressure switch goes off.

There may still be air in the ground loop.

Deaerate the ground loop.

There may be a leak in the refrigerant 
loop.

Contact the manufacturer.

The fluid level in the ground loop fill 
container drops suddenly after startup.

There is a leak in the system (the smell of 
ethyl alcohol is strong), there is a leak in 
the ground loop or there is still air in the 
ground loop.

Check the condition of valves in the 
deaeration group on the air lock and the 
shaft seal on the ground loop pump and, 
if possible, the ground loop extension 
joints, or deaerate. 

Thermal relays go off when starting.

The compressor or the ground loop pump is 
short-circuited or one of the phases is not 
activated.

Check electrical connections.

Fuses in the master switchboard of the 
building are faulty.

Check and replace fuses as required. 

 
 
 
 
 
 
 
 

Содержание T 10-15

Страница 1: ...USER MANUAL L MP SS T P 10 31 L MP SS 5 2013 Ground Source Heat Pumps Since 1983 As Long As the Sun Exists Let Mother Earth Heat Your Home...

Страница 2: ...2 Ground Source Heat Pumps Since 1983...

Страница 3: ...ing and de aeration of the ground loop 7 2 5 Boiler connection 9 2 6 Heating connection 10 2 7 Domestic water connection and circulation of water 10 2 8 HEPAC check list 10 2 9 Electrical installation...

Страница 4: ...ians In L mp ss T and P models to prevent a compressor breakdown the compressor and water in the storage tank must be preheated for 6 hours before the heat pump is started for the first time Press the...

Страница 5: ...metres deep in the ground or at least 3 metres deep in water The bore well is normally 100 200 metres deep with a diameter of 140 165 mm The heat pump is used in the transfer of heat from the water a...

Страница 6: ...d sensors are included in the delivery the heat pump has been correctly fitted the assemblies on top of the heat pump are intact the fuse size is correct for the main fuse and the heat pump see techni...

Страница 7: ...mp ss T 21 31 L mp ss T 21 31 1 2 Collector pipe assemblies on the side Connect asseblies to the collector pipe with care 1 Collector pipe flow 1 uk 2 Collector pipe return 1 uk 1 2 2 4 Filling and de...

Страница 8: ...pes 7 Use the brine pump of the ground source heat pump to accelerate the circulation Turn the main switch Q1 and the heating switch S2 on Turn the switch S4 Auto 0 Maal mp to the position 0 compresso...

Страница 9: ...can be heard from the pipes Please note Deaeration usually takes several hours and helps ensure that all the air is removed from the system and that there are no malfunctions once the system is start...

Страница 10: ...piping through the water tank fill and deaerate the network until all the air has been removed and leave the pressure at 1 1 2 bar maximum values heating network 1 5 bar DHW network 9 bar 2 7 Domesti...

Страница 11: ...ay up the wall of the building near the corner A sensor should not be placed under a roof in a place protected from the wind or over a vent doors or windows where the temperature is not the normal out...

Страница 12: ...pump 1 S5 Heat distribution pump 2 S3 AUTO 0 MAAL MP S4 Condenser pump and magnetic valve QM1 Compressor QM2 Brine pump 2 12 Before startup Before startup check that the heating system has been connec...

Страница 13: ...l valves are in the closed position and that the intermediate valve is open The compressor runs for a little while and the steam pressure switch goes off There may still be air in the ground loop Deae...

Страница 14: ...measured value at the bottom and at the top of the water tank A minimum value is determined for each set value in the Set values section In practice consumption of hot water also starts the compressor...

Страница 15: ...aused a fault in the condenser causing the temperature to drop from the actual values The regulator must be replaced not under warranty The regulator motor has been set on manual and the regulation do...

Страница 16: ...or 0 C 4 2 Space requirements The heat pump requires 50mm more floor space to the side of assemblies than its external dimensions L mp ss T10 T31 and P10 31 geothermal heat pumps are 1 3 1 4 metres in...

Страница 17: ...d warranty certificate and a certificate signed by the user stating that the mechanic instructed the user on how to operate the equipment NOTICE THE WARRANTY OF THE L MP SS T COMPRESSOR IS NOT VALID I...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...L MP SS is a registered trademark of Suomen L mp pumpputekniikka Oy All rights reserved Suomen L mp pumpputekniikka Oy Unikontie 2 FI 62100 LAPUA FINLAND www lampoassa com R...

Отзывы: