Lambrecht PRO-Modbus 14523 Скачать руководство пользователя страница 8

(14523/14524) PRO-Modbus 

  

 

     Manual

Manual
Wind Sensors PRO-Modbus (14523/14524)

10.7  Mapping register for autoconfi guration 

Registers address 46001-49000 containing for each sensor the available registers with measured values and sensor data 
from the range 30001-35000.

The registers can only be read out as a block! The length of the block or the number of available mapping registers 
is in holding register 46000.

For example, in the PRO-Modbus wind speed sensor, registers 46001 to 46004 contain valid addresses. The holding register 
46000 contains the number of registers 4. All 4 registers must be read out in the block with the instruction 

0x04

. Too many 

registers or too few lead to an error message.

10.8  Autoconfi guration

The Modbus sensors from LAMBRECHT meteo off er the possibility of auto-confi guration. This is supported e.g. by the data 
logger met[LOG]. 
For the autoconfi guration, the register addresses of the measured values and sensor data available in the register range 
30001 to 35000 are listed as consecutive values in the LAMBRECHT sensors in register range 46001 to 49000. Registers 
46001 to 49000 can only be read out as a block! The length of the block or the number of available mapping registers is in 
holding register 46000.
Since the addresses from the range 30001 to 35000 apply to all LAMBRECHT sensors, an address from this range is also 
representative of a measured value type.
For example, register 30401 always contains the current value of the air temperature. If this register address is not included 
in the list in register range 46001 to 49000, the connected Modbus sensor does not supply an air temperature.
If the autoconfi guration is started with the data logger met[LOG], it queries the available mapping registers on each COM 
interface in the device address range 1...25. For this purpose, the number of mapping registers is read from register 46000 
and the register range from 46001 is read out as a block. 
The following table contains the assignment of the confi guration to the individual (possible) instantaneous value registers of 
the sensors. Some sensors deliver registers with mean, minimum and maximum values or additional values beyond this speci-
fi cation. Unknown register addresses (or registers that are not required) must therefore be ignored during autoconfi guration.

Register 
address

Parameter name

Unit

Factor Description

Data 
type

Func-
tion 
code

Storage-
type
>16 bit

30001 Wind speed instanta-

neous value

m/s

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30201 Wind direction instan-

taneous value

°

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30401 Air temperature in-

stantaneous valuet

°C

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30601 Humidity instantane-

ous value

% r.F.

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30701 Dew point instantane-

ous value

°C

10

1 decimal place

INT

0x04

Big-Endian 
WORD

30801 Air pressure instanta-

neous value

hPa

10

1 decimal place

INT

0x04

Big-Endian 
WORD

31001 Precipitation amount 

total

mm

10

1 decimal place

INT

0x04

Big-Endian 
WORD

31101 Precipitation amount 

total (High-WORD)

mm

1000

3 decimal places
Registers 31101 + 31102 can 
only be read out together. (func-
tion code 0x04)

uLONG

0x04

Big-Endian 
WORD

31102 Precipitation amount 

total (Low-WORD)

0x04

Big-Endian 
WORD

31201 Precipitation intensity 

1-minute (sliding)

mm/
min

1000

= average (1-min.)
3 decimal places
Time base = 1 min.
Meas. rate = 6x per min.

INT

0x04

Big-Endian 
WORD

31401 Global radiation in-

stantaneous value

W/m²

10

1 decimal place

INT

0x04

Big-Endian 
WORD

8

Содержание PRO-Modbus 14523

Страница 1: ...easuring range of 60 m s low starting values of 0 5 m s high resolution of measuring values very low needs of maintenance Standards EMC acc to EN 61000 6 2 EN 61000 6 4 EN 61000 4 2 3 4 5 6 11 Namur N...

Страница 2: ...an undisturbed terrain of this kind does not exist the sensor must be put up at a height of at least 5 m above the obstacle height If the sensor must be installed on a roof top the place of instal lat...

Страница 3: ...orientation select a landmark which is as far as possible up north with regard to the nal position of the wind direction sensor The reference point can be selected using a topographical map 1 25000 T...

Страница 4: ...14523 14524 PRO Modbus Manual Manual Wind Sensors PRO Modbus 14523 14524 8 Wiring diagram 4...

Страница 5: ...14523 14524 PRO Modbus Manual Manual Wind Sensors PRO Modbus 14523 14524 9 Dimensional drawings Accessory optional Mast adapter Id No 32 14567 008000 5 15 P51 69 P M27x1 5...

Страница 6: ...234 is transmitted in the order 0x12 0x34 Example Big Endian 32 bit or 64 bit Register size value 32 bits 0x12345678 is transmitted in the order 0x12 0x34 0x56 0x78 10 2 Device address The addresses 1...

Страница 7: ...mal place INT 30202 Wind direction average value since last retrieval 10 1 decimal place INT 30203 Wind direction maximum value 10 1 decimal place INT 30204 Wind direction minimum value 10 1 decimal p...

Страница 8: ...tocon guration is started with the data logger met LOG it queries the available mapping registers on each COM interface in the device address range 1 25 For this purpose the number of mapping register...

Страница 9: ...Big Endian WORD 31592 Global radiation instantaneous values Low WORD uncompensated 0x04 Big Endian WORD 10 8 1 Mapping register PRO Modbus Register address Register value Unit Factor Description 4600...

Страница 10: ...delivery 1 sensor without cable Connectable to Lambrecht meteo data loggers power supply units user speci c evaluation systems not included in delivery Parameters Wind direction 14523 Wind speed 14524...

Отзывы: