DHW temperature adjustment
Press the Info button (detail 11 - fig. 1) until displaying the parameter
u02
of the user settings menu.
Press Enter (detail 8 - fig. 1): the actual value of the parameter
u02
is displayed.
Use the buttons (details 9 and 10 - fig. 1) to adjust the temperature from a min. of 10°C to a max. of 65°C.
Press Enter (detail 8 - fig. 1) to confirm the setting.
Then press the Info button (detail 11 - fig. 1) until exiting the menu.
Summer/Winter Switchover
Press the Info button (detail 11 - fig. 1) until displaying the parameter
u03
of the user settings menu.
Press Enter (detail 8 - fig. 1): the actual value of the parameter
u03
is displayed.
Use the buttons (details 9 and 10 - fig. 1) to set Summer mode (0) or Winter mode (1).
Press Enter (detail 8 - fig. 1) to confirm the setting.
Then press the Info button (detail 11 - fig. 1) until exiting the menu.
ECO/COMFORT selection
Heating/hot water tank temperature maintaining (Comfort) can be excluded by the user.
If excluded (Economy), domestic hot water will not be delivered.
Press the Info button (detail 11 - fig. 1) until displaying the parameter
u04
of the user settings menu.
Press Enter (detail 8 - fig. 1): the actual value of the parameter
u04
is displayed.
Use the buttons (details 9 and 10 - fig. 1) to set Economy (0) or Comfort (1) mode.
Press Enter (detail 8 - fig. 1) to confirm the setting.
Then press the Info button (detail 11 - fig. 1) to exit the menu.
Burner Max. Power
Press the Info button (detail 11 - fig. 1) until displaying the parameter
u05
of the user settings menu.
Press Enter (detail 8 - fig. 1): the actual max power step is displayed.
Use the buttons (details 9 and 10 - fig. 1) to vary the max power: from 1 (min Step) to 5 (max Step).
Table. 2 Burner max. power
Press Enter (detail 8 - fig. 1) to confirm the setting.
Then press the Info button (detail 11 - fig. 1) to exit the menu
Burner operation methodology
Press the Info button (detail 11 - fig. 1) until displaying the parameter
u06
of the user settings menu.
Press Enter (detail 8 - fig. 1): the actual value of the parameter
u06
is displayed.
Use the buttons (details 9 and 10 - fig. 1) to vary the operation methodology:
•
u06=0 (default):
Burner activation with request contact (230Vac) or with Room Thermostat contact (voltage-free). (Re-
mote Control request by-passed).
•
u06=1:
Burner activation from Remote Control or with request contact (230Vac).
•
u06=2:
Burner activation from Remote Control and with request contact (230Vac).
Press Enter (detail 8 - fig. 1) to confirm the setting.
Then press the Info button (detail 11 - fig. 1) to exit the menu.
Parameter value
ECO 3,4 P N
Power - kW
ECO 5,5 P N
Power - kW
1
14
30
2
20
36
3
25
41
4
30
48
5
34
55