background image

Taura 24 MCS W TOP

23

If the unit is enclosed in furniture or mounted alongside, there must be space for removing the casing and 
for normal maintenance work.

2.3 Plumbing connections

The heating capacity of the unit should be previously established by calculating the building’s heat requirement ac-
cording to current regulations. The system must be equipped with all its components for it to work properly. It is 
advisable to install on-off valves between the boiler and heating system allowing the boiler to be isolated from the 
system if necessary. 

The safety valve outlet must be connected to a funnel or collection pipe to prevent water flowing out onto 
the ground in the event of over-pressure in the heating circuit. If this is not done, and the drain valve trips 
and floods the room, the boiler manufacturer is not to be held responsible.
Do not use the water system pipes to earth electrical appliances.

Before installation, carefully wash all the pipes of the system to remove residues or impurities that could affect the 
unit’s good working.
Make the connections to the corresponding connections as shown in fig. 6 in chap. IV and with the symbols on the 
unit. A plumbing kit is available on request.

Characteristics of the water system

In the presence of water harder than 25° Fr, we recommend the use of suitably conditioned water in order to avoid 
possible scaling in the boiler. Water treatment is indispensable in the case of very large systems or with frequent 
introduction of replenishing water in the system. If partial or total emptying of the system becomes necessary under 
these conditions, it is advisable to refill it with treated water.

Antifreeze system, antifreeze fluids, additives and inhibitors.

The boiler is equipped with an antifreeze system that turns on the boiler in heating mode when the system delivery 
water temperature falls under 6°C. The device will not come on if the electricity and/or gas supply to the unit are cut 
off. If it becomes necessary, it is permissible to use antifreeze fluid, additives and inhibitors only if the manufacturer 
of these fluids or additives guarantees they are suitable for this use and cause no damage to the heat exchanger 
or other components and/or materials of the boiler unit and system. It is prohibited to use generic antifreeze fluid, 
additives or inhibitors that are not expressly suited for use in heating systems and compatible with the materials of 
the boiler unit and system.

2.4 Gas connection

Before making the connection, ensure that the unit is arranged for operation with the type of fuel available 
and carefully clean all the pipes of the gas system to remove any residues that could affect good functioning 
of the boiler. 

The gas must be connected to the relative connector (see fig. 7) in conformity with current standards, with rigid metal 
pipes or with continuous flexible s/steel wall tubing, placing a gas cock between the system and the boiler. Make 
sure that all the gas connections are tight.
The capacity of the gas meter must be sufficient for the simultaneous use of all equipment connected to it. The 
diameter of the gas pipe leaving the boiler does not determine the diameter of the pipe between the unit and the 
meter; it must be chosen according to its length and loss of head, in conformity with current standards.

Do not use the gas pipes to earth electrical appliances.

Содержание Taura 24 MCS W TOP

Страница 1: ...DE GAS CON C MARA ESTANCA PARA AGUA SANITARIA Y CALEFACCI N CALDEIRA MURAL A G S C MARA ESTANQUE PARA PRODU O DE GUA QUENTE SANIT RIA E AQUECIMENTO cod 3540D95 0 ediz 06 2006 AZIENDA CERTIFICATA ISO 9...

Страница 2: ...nit breaks down and or functions poorly deactivate it do not make any attempt to repair it or directly intervene Contact profession ally qualified personnel Any repair replacement of products must onl...

Страница 3: ...iency heat generator for heating and hot water production running on natural or liquefied petroleum gas equipped with an open flue burner with electronic ignition airtight chamber with forced ventilat...

Страница 4: ...s Water system pressure adjustment The filling pressure with the system cold read on the boiler water gauge must be about 1 0 1 5 bar If the system pressure falls to values below the minimum bring it...

Страница 5: ...y under these conditions it is advisable to refill it with treated water Antifreeze system antifreeze fluids additives and inhibitors The boiler is equipped with an antifreeze system that turns on the...

Страница 6: ...city line The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3 mm interposing fuses of max 3A bet...

Страница 7: ...for coaxial pipes Insert the diaphragm on the aluminium section 60 of the upper flange of the boiler Diaphragm for separate pipes Insert the diaphragm under the flanged air inlet section 80 84 Connec...

Страница 8: ...tion protection air end piece 80 2 Rooftop outlet 80 125 TEE reduction for separate ducts 12 Caution use solely Lamborghini Caloreclima fume suction outlet kits Air suction 80 Air diaphragm Air Fumes...

Страница 9: ...ct WINTER yellow LED on select RESET for 5 seconds LEDs blinking fast for two seconds select WINTER turn the hot water knob ref 2 fig 1 onto minimum for Natural Gas operation or onto maximum for LPG o...

Страница 10: ...00 100 2 Gas type selection 0 Natural gas 1 LPG 0 Natural gas 3 Lighting Power 0 60 50 4 Heating idle time 0 0minutes 1 2 5 minutes 1 2 5 minutes 5 Heating pump Post Circulation 0 0minutes 1 2 5 minut...

Страница 11: ...onds turn to Winter when the 3 LEDs blink fast Selector turned to Reset for 5 seconds turn to Winter when the 3 LEDs blink fast Selector turned to Reset for 5 seconds turn to Winter when the 3 LEDs bl...

Страница 12: ...OFF OFF Natural gas ON BL OFF OFF LPG Red Green Yellow Lighting power OFF OFF OFF 00 06 ON BL OFF OFF 06 13 OFF OFF ON BL 13 21 ON BL OFF ON BL 21 29 OFF ON BL OFF 29 36 ON BL ON BL OFF 36 44 OFF ON B...

Страница 13: ...ated on the meter corresponds to that given in the technical data table in chap 4 Make sure that with no call for heating the burner correctly ignites on opening a hot water tap Check that during heat...

Страница 14: ...hot water temperature to maximum 4 Wait 10 15 minutes for the boiler to stabilize 5 Take the measurement Analyses made with an unstabilized boiler can cause measurement errors Air Fumes Fig 5 Opening...

Страница 15: ...Tap water sensor fault Fault Possible cause Cure Green Yellow Red Heating sensor damaged No circulation of water in the system Air in the system Check the gas flow to the boiler is regular Check the w...

Страница 16: ...ig 6 Top view Bottom view Key 1 Heating system delivery 3 4 2 Hot water outlet 1 2 3 Gas inlet 1 2 4 Tap water inlet 1 2 5 Heating system return 3 4 If using the LEJ LINE plumbing kit the distances fo...

Страница 17: ...amber 20 Burner assembly 21 Main nozzle 22 Burner 26 Combustion chamber insulation 27 Copper exchanger for heating and hot water 28 Fume manifold 29 Fume outlet manifold 32 Heating circulator 34 Heati...

Страница 18: ...nozzles G31 mm 11x0 79 LPG supply pressure G31 mbar 37 0 Pressure at LPG burner G31 mbar 35 0 5 0 LPG delivery G31 kg h 2 00 0 65 Heating Maximum working temperature in heating C 90 Maximum working p...

Страница 19: ...FUSE CAUTION Before connecting the room thermostat or the remote timer control remove the jumper on the terminal block Fig 8 Key 16 Fan 32 Heating circulator 34 Heating temp sensor 38 Flow switch 42...

Страница 20: ...per l evoluzione del prodotto The illustrations and data given are indicative and are not binding on the manufacturer LAMBORGHINI reserves the right to make those changes considered necessary for the...

Отзывы: