Taura 24 MCS W TOP
30
After establishing the parameter to be set, use the following conversion tables to understand the value being set, ac-
cording to the blinking of the LEDs. OFF means LED off, ON means LED on, whereas ON BL means LED blinking.
Red
Green
Yellow
Max. heating power
OFF
OFF
OFF
00-11%
ON BL
OFF
OFF
11-23%
OFF
OFF
ON BL
23-36%
ON BL
OFF
ON BL
36-49%
OFF
ON BL
OFF
49-61%
ON BL
ON BL
OFF
61-74%
OFF
ON BL
ON BL
74-85%
ON BL
ON BL
ON BL
85-100%
Red
Green
Yellow
Gas type selection
OFF
OFF
OFF
Natural gas
ON BL
OFF
OFF
LPG
Red
Green
Yellow
Lighting power
OFF
OFF
OFF
00-06%
ON BL
OFF
OFF
06-13%
OFF
OFF
ON BL
13-21%
ON BL
OFF
ON BL
21-29%
OFF
ON BL
OFF
29-36%
ON BL
ON BL
OFF
36-44%
OFF
ON BL
ON BL
44-51%
ON BL
ON BL
ON BL
51-60%
Red
Green
Yellow
Heating idle time
OFF
OFF
OFF
00 minutes
ON BL
OFF
OFF
2.5 minutes
Red
Green
Yellow
Pump post-circulation
OFF
OFF
OFF
00 minutes
ON BL
OFF
OFF
2.5 minutes
Red
Green
Yellow
Heating max. setpoint
OFF
OFF
OFF
30°C
ON BL
OFF
OFF
40°C
OFF
OFF
ON BL
85°C
Red
Green
Yellow
Hot water max. setpoint
OFF
OFF
OFF
55°C
ON BL
OFF
OFF
65°C
Red
Green
Yellow
Hot water burner shutdown
OFF
OFF
OFF
Fixed shutdown
ON BL
OFF
OFF
Tied to user setpoint