iXinox 24 C
25
EN
cod. 3541N452EN - Rev. 03 - 03/2020
b08
Hours without DHW drawn
(b01=1)
0-24 hours (time for temporary deactivation of comfort mode
without drawing)
24 hours
No effect on adjustment (b01=2)
0-24 hours (time for temporary deactivation of comfort mode
without drawing)
24 hours
Hours without DHW drawn
(b01=3)
0-24 hours (time for temporary deactivation of comfort mode
without drawing)
24 hours
No effect on adjustment (b01=4)
0-24 hours (time for temporary deactivation of comfort mode
without drawing)
24 hours
b09
Fault 20 status selection
0=Deactivated, 1=Enabled (Only for versions with pressure
transducer)
0=Deactivated
b10
Comfort burner on time (b01=1)
0-40 seconds
15 seconds
Not implemented (b01=2)
--
--
Not implemented (b01=3)
--
--
Not implemented (b01=4)
--
--
b11
Flowmeter timing (b01=1)
0=Deactivated, 1-10=seconds
0=Deactivated
Storage tank preparation mode
(b01=2)
0=Fixed primary, 1=Linked to setpoint, 2=Ramp
0=Fixed primary
Flowmeter timing (b01=3)
0=Deactivated, 1-10=seconds
0=Deactivated
Storage tank preparation mode
(b01=4)
0=Fixed primary, 1=Linked to setpoint, 2=Ramp
0=Fixed primary
b12
Modulation delta (b01=1)
0-30°C/10
0°C/10
Priority override - Activation
(b01=2)
0-255 minutes
30 minutes
Modulation delta (b01=3)
0-30°C/10
0°C/10
Priority override - Activation
(b01=4)
0-255 minutes
30 minutes
b13
Not implemented (b01=1)
--
--
Priority override - Deactivation
(b01=2)
0-255 minutes
15 minutes
Not implemented (b01=3)
--
--
Priority override - Deactivation
(b01=4)
0-255 minutes
15 minutes
b14
Pump antiblock operation time
0-20 seconds
5 seconds
b15
Flowmeter type selection (b01=1) 0=Flow. (450 imp/l), 1=Flow. (700 imp/l), 2= Flow. (190 imp/l)
2= Flowmeter (190 imp/l)
No effect on adjustment (b01=2)
0=Flow. (450 imp/l), 1=Flow. (700 imp/l), 2= Flow. (190 imp/l)
2= Flowmeter (190 imp/l)
Flowmeter type selection (b01=3) 0=Flow. (450 imp/l), 1=Flow. (700 imp/l), 2= Flow. (190 imp/l)
2= Flowmeter (190 imp/l)
No effect on adjustment (b01=4)
0=Flow. (450 imp/l), 1=Flow. (700 imp/l), 2= Flow. (190 imp/l)
2= Flowmeter (190 imp/l)
b16
Fan frequency in standby mode
0-100%
0%
b17
Summer/Winter symbol
0 = Disabled, 1 = Enabled
0 = Disabled
b18
DHW mode activation flow rate
(b01=1)
0-100L/min/10
25
No effect on adjustment (b01=2)
0-100L/min/10
25
DHW mode activation flow rate
(b01=3)
0-100L/min/10
25
No effect on adjustment (b01=4)
0-100L/min/10
25
b19
DHW mode deactivation flow rate
(b01=1)
0-100L/min/10
20
No effect on adjustment (b01=2)
0-100L/min/10
20
DHW mode deactivation flow rate
(b01=3)
0-100L/min/10
20
No effect on adjustment (b01=4)
0-100L/min/10
20
b20
Flue material selection
0=Standard, 1=PVC, 2=CPVC
0=Standard
b21
PVC flue maximum temperature
60-110°C
88°C
b22
CPVC flue maximum tempera-
ture
60-110°C
93°C
b23
Standard flue shutdown maxi-
mum temperature
60-110°C
100°C
b24
PVC flue shutdown maximum
temperature
60-110°C
93°C
Contents
Description
Range
Default