10.6.16 Setting parameters
Order number
Code
State
Def ault
Minumum
Maximum
Setting
interval
Unit
1.1
DHW MODE
Enable or disable the DHW mode:0=NON,1=YES
1
0
1
1
/
1.2
DISINFECT
Enable or disable the disinf ect mode:0=NON,1=YES
1
0
1
1
/
1.3
DHW PRIORITY
Enable or disable the DHW priority mode:0=NON,1=YES
1
0
1
1
/
1.4
DHW PUMP
Enable or disable the DHW pump mode:0=NON,1=YES
0
0
1
1
/
1.5
DHW PRIORITY TIME SET Enable or disable the DHW priority time set:0=NON,1=YES
0
0
1
1
/
1.6
dT5_ON
The temperature dif f erence f or starting the heat pump
10
1
30
1
ć
1.7
dT1S5
The correct value to adjust the output of the compressor.
10
5
40
1
ć
1.8
T4DHWMAX
The maximum ambient temperature that the heat pump
can operate at f or domestic water heating
43
35
43
1
ć
1.9
T4DHWMIN
The minimum ambient temperature that the heat pump can
operate f or domestic water heating
-10
-25
5
1
ć
1.10
t_INTERVAI_DHW
the start time interval of the compressor in DHW mode.
5
5
5
1
MIN
1.11
dT5_TBH_ OFF
the temperature dif f erence between T5 and T5S that
turns the booster heater of f .
5
0
10
1
ć
1.12
T4_TBH_ON
the highest outdoor temperature the TBH can operate.
5
-5
20
1
ć
1.13
t_TBH_DELAY
the time that the compressor has run before starting the
booster heater
30
0
240
5
MIN
1.14
T5S_DI
the target temperature of water in the domestic hot water
tank in the DISINFECT f unction.
65
60
70
1
ć
1.15
t_DI_HIGHTEMP.
the time that the highest temperature of water in the
domestic hot water tank in the DISINFECT f unction will
last
15
5
60
5
MIN
1.16
t_DI_MAX
the maximum time that disinf ection will last
210
90
300
5
MIN
1.17
t_DHWHP_RESTRICT
he operation time f or the space heating/cooling operation.
30
10
600
5
MIN
1.18
t_DHWHP_MAX
the maximum continuous working period of the heat pump
in DHW PRIORITY mode.
90
10
600
5
MIN
1.20
PUMP RUNNING TIME
the certain time that the DHW pump will keep running f or
5
5
120
1
MIN
1.19
DHW PUMP TIME RUN
Enable or disable the DHW pump run as timed and keeps
running f or PUMP RUNNING TIME:0=NON,1=YES
1
0
1
1
/
1.21
DHW PUMP DISINFECT
Enable or disable the DHW pump operate when the unit is
in disinf ect mode and T5 T5S_DI-2:0=NON,1=YES
1
0
1
1
/
2.1
COOL MODE
Enable or disable the cooling mode:0=NON,1=YES
1
0
1
1
/
2.2
t_T4_FRESH_C
The ref resh time of climate related curves f or cooling
mode
0.5
0.5
6
0.5
hours
2.3
T4CMAX
The highest ambient operation temperature f or cooling
mode
52
35
52
1
ć
2.4
T4CMIN
the lowest ambient operating temperature f or cooling
mode
10
-5
25
1
ć
2.5
dT1SC
the temperature dif f erence f or starting the heat pump(T1)
5
2
10
1
ć
2.6
dTSC
the temperature dif f erence f or starting the heat pump(Ta)
2
1
10
1
ć
2.8
T1SetC1
The setting temperature 1 of climate related curves f or
cooling mode.
10
5
25
1
ć
2.9
T1SetC2
The setting temperature 2 of climate related curves f or
cooling mode.
16
5
25
1
ć
2.10
T4C1
The ambient temperature 1 of climate related curves f or
cooling mode.
35
-5
46
1
ć
2.11
T4C2
The ambient temperature 1 of climate related curves f or
cooling mode.
25
-5
46
1
ć
2.12
ZONE1 C-EMISSION
The type of zone1 end f or cooling mode
˖
0=FCU(f an coil
unit)
ˈ
1=RAD.(radiator)
ˈ
2=FLH(f loor heating)
0
0
2
1
/
2.13
ZONE2 C-EMISSION
The type of zone2 end f or cooling mode
˖
0=FCU(f an coil
unit)
ˈ
1=RAD.(radiator)
ˈ
2=FLH(f loor heating)
0
0
2
1
/
The parameters related to this chapter are shown in the table below.