83-507-013 Rev. A
47
For resistive programming, internal current sources, for Output Voltage and/or Output Current control,
supply 1mA current through external programming resistors connected between J1-9 & 22 and J1-10 &
23. The voltage across the programming resistors is used as a programming voltage for the power sup-
ply. Resistance of 0
i
5Kohm or 0
i
10Kohm can be selected to program the Output Voltage and Output
Current from zero to full scale.
A variable resistor can control the output over its entire range, or a combination of variable resistor and
series/parallel resistors can control the output over restricted portion of its range.
Perform the following procedure to set the power supply to Resistive programming:
1. Turn the AC On/Off switch to Off.
2. Set setup switch SW1, positions 1 and 2 to their UP position.
3. Set SW1, position 3 to select the programming resistor range according to Table 6-4.
4. Set SW1, positions 7 and 8 to their UP position, to enable resistive programming mode.
5. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming resistors to the mating plug of J1 as shown in Fig.6-2.
7. Set the programming resistors to the desired resistance and turn the power supply ON. Adjust the
resistors to change the power supply output.
NOTES:
1. SW1, positions 4, 5, 6 and 9 are not required for remote programming. Their settings can be deter-
mined according to the application requirements.
2. The control circuits allow the user to set the Output Voltage and Output Current up to 5% over the
model-rated maximum value. The power supply will operate within the extended range, however it is
not recommended to operate the power supply over its voltage and current rating and performance is
not guaranteed.
3. To maintain the temperature stability specification of the power supply, the resistors used for pro-
gramming should be stable and low noise resistors, with temperature coefficient of less than 50ppm.
4. When resistive programming is used, front panel and computer control (via serial communication
port) of Output Voltage and Current are disabled.
SW1-3 setting
Output Voltage programming
VPGM (J1-9)
Output Current programming
IPGM (J1-10)
UP 0-10Kohm 0-10Kohm
DOWN 0-5Kohm
0-5Kohm
Table 6-4: SW1-3 setting and programming range
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT
1
14
13
25
10
9
23
22
OUTPUT CURRENT
PROGRAMMING
OUTPUT VOLTAGE
PROGRAMMING
J1 connector, rear panel view
Fig.6-2: Remote resistive programming
PROGRAMMING
RESISTOR
PROGRAMMING
RESISTOR
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
UPPER LIMIT
OPTIONAL SETS
UPPER LIMIT
12
8