83-507-013 Rev. A
16
screw, insert the stripped wire into the terminal and tighten the screw securely (4.4-5.3 Lb-inch).
5. Route the wires inside the cover to prevent pinching. Fasten the cover to the unit using the M3x8 Flat Head
screws provided. Refer to Fig.3-3 for details.
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
The following procedure ensures that the power supply is operational and may be used as a basic
incoming inspection check. Refer to Fig. 4-1 and fig. 4-2 for the location of the controls indicated in the
procedure.
3.8.2 Prior to Operation
1. Ensure that the power supply is configured to the default setting:
−
On/Off switch at Off position.
−
Dip switch: All positions at Down (“Off”) position.
−
J2 Sense connector: Configured to Local Sense as shown in Fig. 3-4:
−
For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default) posi-
tion (Refer to Fig.4-2, Item 9 for location) if checkout is to be done in IEEE mode.
2. Connect the unit to an AC source as described in Section 3.7.
Fig.3-3: AC input cover and strain relief, 1500W models
Cover
Assembled Strain Relief
M3x8
Flat Head screws
(2 places)
L N
1 Remote (+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense
Fig.3-4: J2 Sense connector default connection
Plug P/N: MC1,5/5-ST-3,81
(Phoenix)