83-515-000 Rev. A
22
WARNING
Hazardous voltages exist at the outputs and the load connections. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.
Shield
M10x25 screw (2 places)
Hex Nut (2 places)
Flat washer (2 places)
Spring washer (2 places)
Wire terminal lug (2 places)
Flat washer
(2 places)
Screws tightening torque: 290-310 Lb-inch.
Fig. 3-6: Load wires connection, 8V to 100V models
Fig. 3-7: Bus-bars shield mounting
150V to 600V Models
The 150V to 600V models have a four terminal wire clamp output connector. The two left terminals
are the positive outputs and the two right terminals are the negative outputs. Max. 30A per terminal.
The connector requirements are as follows: