83-515-000 Rev. A
19
3.9 CONNECTING THE LOAD
3.9.1 Load
Wiring
The following considerations should be made to select wiring for connecting the load to the power
supply:
∗
Current carrying capacity of the wire (refer to Section 3.9.2)
∗
Insulation rating of the wire should be at least equivalent to the maximum output voltage of the
power supply.
∗
Maximum wire length and voltage drop (refer to Section 3.9.2)
∗
Noise and impedance effects of the load wiring (refer to Section 3.9.4).
3.9.2 Current Carrying Capacity
Two factors must be considered when selecting the wire size:
1. Wires should be at least heavy enough not to overheat while carrying the power supply load
current at the rated load, or the current that would flow in the event the load wires were
shorted, whichever is greater.
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated
current. Although units will compensate for up to 5V in each load wire, it is recommended to
minimize the voltage drop (1V typical maximum) to prevent excessive output power consump-
tion from the power supply and poor dynamic response to load changes. Please refer to Ta-
bles 3-2 and 3-3 for maximum wire length (to limit voltage drop) in American and European di-
mensions respectively.
Maximum length in Feet to limit
voltage drop to 1V or less
Wire size
AWG
Resistivity
OHM/1000ft
10A 20A 50A 100A
200A 400A
14 2.526
40
20
8
4
2
---
12 1.589
60
30
12
6
3
---
10 0.9994
100
50
20
10
5
2
8 0.6285
160
80
32
15
8
4
6
0.3953 250
125
50 25 12 6
4
0.2486 400 200 80 40 20 10
2 0.1564
600
300
125
60
30
15
0
0.0983 1000
500
200 100 50 25
Table 3-2: Maximum wire length for 1V drop on lead (in feet)
WARNING
Turn Off the AC input power before making or changing any
rear panel connection. Ensure that all connections are se-
curely tightened before applying power. There is a potential
shock hazard when using a power supply with a rated output
greater than 40V.
Содержание 2U GENESYS 5kW
Страница 2: ......
Страница 3: ...GENESYS Manual Supplement FOR UNITS EQUIPPED WITH IEMD OPTION ALSO REFER TO MANUAL 83 030 200 IEMD...
Страница 8: ......
Страница 16: ...83 515 000 Rev A 9 CHAPTER 2 SPECIFICATIONS...
Страница 17: ...83 515 000 Rev A 10...
Страница 19: ...83 515 000 Rev A 12 2 13 GENESYSTM 5000W POWER SUPPLIES OUTLINE DRAWINGS...