Alarm Thresholds
The Alarm Thresholds setting allows the user to determine the current or voltage value at which an alarm trigger.
The threshold can be changed for Low Current Alarm, Low Current Alarm Reset, Overload Alarm, Low Voltage
Alarm, Low Voltage Alarm Reset, End of Discharge Alarm, High Voltage Alarm, and High Voltage Shutdown Alarm.
NOTE:
Alarm threshold defaults are based on the charger output. The alarm threshold values shown above are
not representative of the default values for any specific A36D charger.
Summary Alarm Selects
The Summary alarm selects setting allows the user to choose whether or not to include the Low Current Alarm,
Ground Detection Alarms, and AC Failure Alarm as part of the Summary Alarm. By default, all three of these
alarms are included in the Summary Alarm.
NOTE:
The Low DC Voltage and High DC Voltage alarms are included in the Summary alarm and cannot be
removed.
3.4.1.3 Advanced Settings
The Advanced Settings Menu allows the user to access and modify other parameters of the charger which are not
included in the basic Settings Menu. The Advanced Settings Menu is divided into 7 submenus: “Equalize Timer
Settings”, “Advanced Alarm Settings”, “Temperature Compensation”, “Ground Detection Alarm Enable”,
“Communication Settings”, “LCD Settings”, and “Return to Defaults”.
Equalize Timer Settings
The Equalize Timer Settings submenu provides access to the change the Equalize Timer Mode, and Equalize Timer
Hours.
Equalize Timer Mode
The Equalize timer mode determines when the charger will go into an Equalize charging cycle. The timer modes
are “Auto EQ OFF”, “7 Day Auto EQ”, “14 Day Auto EQ”, “30 Day Auto EQ”, and “Auto EQ on LV”. The default
setting for the Equalize timer mode is Auto EQ OFF. The Equalize Timer Modes are discussed in further detail in
Section 3.3.1.
< Alarm >
Thresholds
< Low DC Current
Alarm 0.2 A
< Low DC Current
Reset 0.4 A
< Overload
Alarm 18.0 A
< Overload
Reset 16.5 A
< Low Voltage
Alarm 118.8 V
< Low Voltage
Reset 8 Percent
< End of
Discharge 100.8V
< End Discharge
Reset 10 Percent
< High Voltage
Alarm 147.0 V
< High Voltage
Reset 135.0 V
< HV Shutdown
Alarm 150.0 V
< Summary >
Alarm Selects
< Low Current >
Alarm in Summary
< AC Fail >
Alarm in Summary
< Gnd. Detect. >
Alarm in Summary
< Equalize >
Timer Mode
< EQ Timer Mode
Auto EQ OFF