Command Pro Engineered Systems
User Manual
24
142134
6.5.2
21R14A Installation Testing
Before putting the system into service, perform the following testing procedure:
1.
Apply power to the receiver.
2.
Verify that the POWER LED turns ON. Refer to
Figure 6
.
3.
Turn the transmitter to ‘ON’.
4.
Verify that the K16 and Output LED turn ON; while the alarm is on, verify the Signal LED flashes.
5.
Verify that voltage is present at the receiver normally open on output for the MLC.
6.
Verify that no voltage is present at any of the relay output terminals that are used for your
application.
7.
If voltage is present at any output terminal that is used, recheck the system wiring.
6.5.3
21R22 Installation Testing
Before putting the system into service, perform the following testing procedure:
1.
Apply power to the receiver.
2.
Verify that the POWER LED and the K23 (MLC) LED both turn ON. Refer to
Figure 10
.
3.
Turn on the transmitter.
4.
Verify that the K23 LED turns OFF.
5.
Verify that the K24 (OPR) LED turns ON and the SIGNAL LED FLASHES. Refer to
Figure 11
.
Figure 10: 21R22 Status LED Indicators - Receiver ON (Transmitter OFF)
Содержание Command Pro SAFE-T-RANGE
Страница 19: ...Command Pro Engineered Systems User Manual 19 142134 Figure 6 21R14A Receiver ...
Страница 20: ...Command Pro Engineered Systems User Manual 20 142134 Figure 7 Typical 21R14A Power Control Wiring ...
Страница 23: ...Command Pro Engineered Systems User Manual 23 142134 Figure 9 Typical 21R22 Power Control Wiring ...
Страница 31: ...Command Pro Engineered Systems User Manual 31 142134 Figure 16 22R08A Series Receiver Relay Output Connections ...