background image

button 

and at the same time 

or  . The exit from the setup takes place automatically after 30 seconds of no button activation or immediately by pressing

button .
The setpoint SP can be displayed and set also during the normal operation status with 

and 

or 

buttons. The setting range however remains within the

limits established with 

SPL

and 

SPH

.

Table 2

4. DISPLAYS

The temperatures measured by probes T1 and T2 are treated by the microprocessor in such a way as to display them in the most meaningful way. To achieve
this, the temperatures can then be corrected by the respective offsets 

OS1

and 

OS2

and displayed in degrees Celsius or Fahrenheit, depending on the value

set to 

SCL

.

Caution:

if you change the readout scale you must then IMPERATIVELY re-configure the parameters relating to the absolute temperatures (SP, DLI, FDR …) and

to the differential temperatures (HYS, ATL, ATH …).
The air temperature, offset by OS1, before being displayed is treated by a special algorithm allowing the simulation of a thermal mass directly propotional to
the value set to 

SIM

. The resulting effect is a hunting reduction on the displayed value.

By setting 

DDY

to values greater than 0, during defrost, instead of the temperature, the display shows DEF, which will remain beyond defrost end for the number

of programmed minutes.

5. THERMOSTAT FUNCTION

5.1

Temperature control is based upon the comparison between temperature T1, the setpoint 

SP

and the hysteresis 

HYS

. The thermostat operation is

determined by the value set to HYS: if greater than 0 there will be COOLING control, if lower than 0 there will be HEATING control, if equal to 0, the thermostat
will be excluded and the corresponding output will be switched off permanently.

Example 1: HYS 02, SP -20; relay Off with T1 -20° and On with T1 -18°.
Example 2: HYS –04, SP 70; relay Off with T1 +70° and On with T1 +66°.

The actual relay on switching is however only possible if since the off switching the minimum rest time 

CRT

has elapsed.

The relay status is signalled by the relevant dot on the display.

5.2

In consequence to failure of probe T1, the display shows ERR and the output is controlled with a fixed time established by 

CDC

. This determines the output

running time within 10 minute cycles.

Example: CDC 06, 6 minutes On, 4 minutes Off.

6. DEFROST

6.1

Defrost automatically starts every time the built-in timer matches the time necessary to obtain the defrost frequency determined with 

DFR

. For example,

with DFR=4 there will be a defrost every 6 hours. With DFR set to 0, the timed defrost function is excluded.
Defrost can be started manually from the Info menu in the following way: select DF, press button 

first then 

simultaneously.

The built-in timer is set to zero every time the unit is switched on (power supply or standby) and every time defrost is started.

6.2

Once that defrost has been started, the outputs are controlled by the parameter 

DTY

according to the following table:

6.3

Defrost terminates either when time 

DTO

elapses or, if the evaporator probe is active (

T2

=YES), when temperature 

DLI

is measured.

Now, if 

DRN

is greater than 0, before cooling starts, all the outputs remain off for the time set to DRN. This phase, called drain down, will allow a complete

ice melting and the drain of the resulting water.

INSTRUCTIONS FOR INSTALLATION AND USE.

SPL

-40.. SPH [°]

minimum temp. set

ATD

0.. 120 [min]

temperature alarm delay

SPH

SPL.. +250 [°]

maximum temp. set

ADD

0.. 120 [min]

door alarm delay

SP

SPL.. SPH [°]

actual temperature set

ACL

0.. 120 [weeks]

condenser clean interval

HYS

-30.. 0.. +30 [°]

thermostat hysteresis

CRT

0.. 30 [min]

compressor rest time

DFR

0.. 24

defrost frequency/24h

CDC

0.. 10

compressor duty cycle

DLI

0.. +70 [°]

defrost end temperature

OFF

YES/NO

standby key enable

DTO

1.. 120 [min]

defrost timeout

DS

YES/NO

door switch enable

DTY

OFF/ELE/GAS

defrost type

LDC

YES/NO

door switched light

DRN

0.. 30 [min]

drain down

T2

YES/NO

probe 2 enable

DDY

0.. 60 [min]

defrost display control

SCL

°C/°F

display scale

FRC

0.. 5

fan run control

OS1

-15.. +15 [°]

probe 1 offset

FDR

-40.. +70 [°]

fan re-start temperature

OS2

-15.. +15 [°]

probe 2 offset

ATL

-25.. 0 [°]

low alarm differential

SIM

0.. 100

display slowdown

ATH

0.. +25 [°]

high alarm differential

ADR

0.. 255

address

DTY

D

EFROST

C

OMPRESSOR

F

ANS

OFF

off

off

on

ELE

on

off

off

GAS

on

on

off

Содержание SMD34RU

Страница 1: ...n table 1 you can see status levels and indications relevant to them 2 1 STANDBY OFF permanently displayed to show the standby status Setting the parameter OFF YES enables the 0 I button that allows to put the SMD90 on standby If OFF NO the button 0 I is inhibited On standby output controls and buttons are excluded with the exception of light command manually or door controlled 2 2 NORMAL during t...

Страница 2: ...ant dot on the display 5 2 In consequence to failure of probe T1 the display shows ERR and the output is controlled with a fixed time established by CDC This determines the output running time within 10 minute cycles Example CDC 06 6 minutes On 4 minutes Off 6 DEFROST 6 1 Defrost automatically starts every time the built in timer matches the time necessary to obtain the defrost frequency determine...

Страница 3: ...ill be stopped too and the alarm will be signalled 8 3 By setting parameter ACL to a value greater than 0 you enable the periodic condenser clean warning This means that when the timer counting the thermostat running time matches the weeks programmed with ACL the display will show a condenser clean request Example with ACL 16 you will obtain a warning every 16x7x24 2688 hours of compressor operati...

Страница 4: ... 041 5460713 INSTRUCTIONS FOR INSTALLATION AND USE SMD90B35E C TERMINAL FUNCTION RATINGS TERMINAL FUNCTION RATINGS L N Power supply 230 Vac 50 60Hz L3 L4 Auxiliary loads 8 3 A 230 Vac L1 L2 Compressor 20 6 A 230 Vac L9 L10 Defrost 8 3 A 230 Vac L5 L6 Evap Fans 8 3 A 230 Vac A1 A2 Alarm 8 3 A 230 Vac A3 L7 Indoor lights 8 3 A 230 Vac WIRING DIAGRAM ...

Отзывы: