BA_060 Rev 1B6 Pressure transmitter PASCAL CS
Page 16/20
LRL
URL
Setting range for
the reset-point
Setting range for
the switch-point
rP
SP
0,5% of MR
Figure 14: Setting ranges for switch-point and reset-point
You can define delays for the switch-point as well as the reset-point, e.g. to avoid that
short pressure peaks trigger the switch.
0
1
t
switch-point (
SP
)
reset-point (
rP
)
delay
switch (
dS
)
delay
reset (
dr
)
Figure 15: Output delays for a hysteresis function normally open (Hno)
When you select a frame function, the menue items for switch-point and reset-point are
replaced by the upper and lower frame limits. The minimum difference of the frame limits is
also 0.5% of the measuring range.
Display
Designation
Description
Frame high
Upper frame limit in the selected measuring unit
Frame low
Lower frame limit in the selected measuring unit
Delay switch
Output delay when entering the frame
Delay reset
Output delay when leaving the frame
Output function
Configuring the output (normally open / normally
closed, hysteresis / frame)
Menue items for second switch point
Return
Return to "
SP
"
Table 12: Menue items for a switching output with frame function