BA_080_en_2022-01_11.02  Pressure transmitter PASCAL CV4 

Page 20/24 

 

6.4.5.4 

Configuration of the table function 

With the table function you can realise any output function (display software version 1.1.0 
and above).  E.g.  you  can  convert  the fill  height  to  the fill  quantity  depending  on  the  tank 
shape. You can use up to 32 interpolation points for this purpose.  

  

Menue entry

 

Description

 

Number of points 

Number of interpolation points 

Table values 

Combination of pressure in per cent and corresponding current 
value that are used as interpolation points of the table function 

Table 14: "Output Table" submenue 

  

You can only edit the table points when the table function is not active. You may need to set 
the output function to "linear", for instance (see above) before editing table points. 

The table points must be sorted according to ascending pressure. For instance, the 20% 
point may not be before the 10% point. Otherwise you cannot activate the table function. 

If the first table point is not set at 0%, the start of the table is calculated by means of the first 
two interpolation points. The same applies when the last table point is not at 100%. 

With the 

- and 

- buttons, you can scroll through the table points and look at the com-

binations of pressure in per cent and current in mA. With OK, you switch to the edit mode 
for the displayed table point. Now enter the first per cent value and then the current value. 
When  you  confirm  the  current  value,  you  return  to  the  display  of  the  table  point  you  just 
edited. 

  

 

Figure 10: Changing the table point 

  

6.4.5.5 

Minimum and maximum current 

In the standard setting, the current output is limited at 3.8 and 20.5 mA, meaning a further 
drop or rise in the measured variable  does not  change the current. You can freely select 
these current limits for the lower limit between 3.8 and 4 mA and for the upper limit between 
20 and 21 mA. 

  

 

 

OK

3x

OK

5x

3x

OK

Содержание CV4110

Страница 1: ...ity with EU Regulations 2 1 4 EX Approval 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Devices with Diaphragm Seal 3 3 2 Differential pressure devices 3 3 3 Mechanical Insta...

Страница 2: ...nded to measure pressure of gases vapors and liquids as specified in the data sheet 1 3 Conformity with EU Regulations The CE marking on the device certifies its compliance with the applicable EU Dire...

Страница 3: ...l measurements it is the lower process connection 3 3 Mechanical Installation Use gaskets if required that are suitable for the process connection and resistant to the media Before starting operation...

Страница 4: ...ock completely downwards before inserting the cable Otherwise it is not possible to ensure a safe electrical connection Do not forget to tighten the cable gland after the electrical connection is fina...

Страница 5: ...rmed in the factory 5 Disassembly When measuring hot media make sure that the device has cooled down prior to any dis mounting or wear appropriate protective clothing to avoid burns Switch off the pow...

Страница 6: ...device The gen eral functionality of the buttons is identical in all operating modes Figure 2 Control elements If you press and hold the up or down button it will automatically be triggered multiple t...

Страница 7: ...value is larger than the displayable number due to setting a fixed decimal point or an inappropriate unit the largest displayable number is shown flashing In this case please select a different setti...

Страница 8: ...d by the header text Menu locked in combination with the lock icon Use the same key combination to unlock the menue again 6 2 3 Icons indicating device status In the top right corner of the display de...

Страница 9: ...lue is shown at the maxi mum size best readability from a dis tance One additional value can also be shown Table 4 Display layouts You can define what information shall be shown in the layout s placeh...

Страница 10: ...by pressing and holding the ESC button for at least one second Figure 4 Navigating the operating menue In long menues and selection lists a scroll bar on the left side shows the position of the curren...

Страница 11: ...and go back to view mode The se lected value is not saved With the OK button the selected value is saved Saving the value is confirmed with an in formation window and the new value is shown in view m...

Страница 12: ...then set to the parameter limit You can set negative numbers by decreasing the value below zero When you press the ESC button you can cancel the entry at any time and return to the display of the set...

Страница 13: ...ystem Device data and function such as factory reset Table 6 The main menue 6 4 2 Menue Quick Setup In Quick Setup basic configuration options are combined to make it possible to quickly con figure ke...

Страница 14: ...calibration in the lab When executing this function the applied pressure will be interpreted as zero bar pressure The zero point correction results in an offset of the whole characteristic curve Ther...

Страница 15: ...ustment should be performed as close as possible to the lower range value and upper range value of the measurement ranges 6 4 3 4 Current adjustment You can use the current adjustment if the reading a...

Страница 16: ...reen mode Configuration of the screen layout and content see 6 2 4 Decimal point Select setting of decimal point to determine number of decimal places Backlight Switch backlight on off Table 10 Displa...

Страница 17: ...psi Pound force per square inch 1 psi 68 9 mbar atm Atmospheric pressure 1 atm 1013 mbar mmH2O Millimetre water column 1 mmH2O 0 0981 mbar mH2O Metre water column 1 mH2O 98 1 mbar inH2O Inch water co...

Страница 18: ...tput Configure the measured value as well as the current output in the Measurement output menue Menue entry Description Damping Setting the damping of the output signal Output function Setting the out...

Страница 19: ...2 Output function You can set the output function proportionally rising to the measured value selection Lin ear or proportionally falling selection Inverse You can also define the output signal by a...

Страница 20: ...pressure For instance the 20 point may not be before the 10 point Otherwise you cannot activate the table function If the first table point is not set at 0 the start of the table is calculated by mean...

Страница 21: ...nt simulation influences only the current output The pressure simulation takes all settings into consideration including the damping 6 4 8 Menue Communication In the Communication menue the settings f...

Страница 22: ...settings Device reset Restarting the device such as after a power outage Table 18 System menue 6 4 9 1 Device ID Using the device ID you can show a custom text in the display if you configure the scre...

Страница 23: ...BA_080_en_2022 01_11 02 Pressure transmitter PASCAL CV4 Page 23 24...

Страница 24: ...version 1 1 0 and above Setting of the pressure value that should correspondto 20 mA endof range Setting the damping of the output signal Selection of the decimal places of the 1st value by specifyin...

Отзывы: